ABB Substation Automation
Products and Systems
Technical Reference Manual
REJ 523
1MRS750940-MUM
27
Table 4.1.3.3-4 SGF3
SGF3/1
SGF3/2
SGF3/3
SGF3/4
SGF3/5
SGF3/6
SGF3/7
SGF3/8
Operation
0
0
0
0
0
0
-
-
Definite-time
1)
1
0
0
0
0
0
-
-
Extremely inverse
0
1
0
0
0
0
-
-
Very inverse
0
0
1
0
0
0
-
-
Normal inverse
0
0
0
1
0
0
-
-
Long-time inverse
0
0
0
0
1
0
-
-
RI-type
characteristic
0
0
0
0
0
1
-
-
RD-type
characteristic
1)
Default setting
Note!
Only one type of characteristic can be selected at a time! If more than one switch is
set active, the characteristic with the lowest weighting factor of the selected switches
will be activated.