REJ 523
Technical Reference Manual
ABB Substation Automation
Products and Systems
MRS750940-MUM
62
Parameters for disturbance recorder
Information
Parameter
Setting range
Default
setting
Customer’s
setting
Event mask for disturbance
recorder
V157
0 / 1
1
Internal trigger signals’
checksum
V241
0...15
8
Internal trigger signal’s edge
V242
0...15
0
External trigger signal
(BI signal)
V243
0 / 1
1
External trigger signal’s edge
V244
0 / 1
0
Post-triggering recording length
V245
0...38
1
Station identification/unit
number
M18
0…9999
0000
Station name
M20
Max 15
characters
- ABB -
Analogue channel conversion
factor and unit, phase currents
M80...82
Factor
0…65535,
unit (A, kV)
00000, --