ABB Substation Automation
Products and Systems
MRS750940-MUM
42
Disturbance recorder
Table 4.1.9.3-4 M parameters for disturbance recorder
Description
Parameter
R/W
Value/Note
Analogue channels in use
M13
R
7 (=00000111B)
Digital channels in use
M14
R
31 (=00011111B)
Sampling rate
M15
R
800 or 960 Hz
Station identification/
unit number
M18
R/W
0…9999
Rated frequency
M19
R
50 or 60 Hz
Station name
M20
R/W
Max 15 characters
Digital channel texts
M40...44
R
Analogue channel texts
M60...62
R
Analogue channel
conversion factor and
unit, phases I
L1
, I
L2
and I
L3
M80…82
1)
R/W
XXXXX, YY
1)
These parameters being set to the default value 0 causes that three dashes are
shown instead of the primary values on the LCD.