![ABB REJ 523 Скачать руководство пользователя страница 55](http://html.mh-extra.com/html/abb/rej-523/rej-523_technical-reference-manual_4937055.webp)
ABB Substation Automation
Products and Systems
Technical Reference Manual
REJ 523
1MRS750940-MUM
55
Table 4.2.3-11 Standard tests
Insulation tests
Dielectric tests
According to IEC 60255-5
•
Test voltage
2 kV, 50 Hz, 1 min
Impulse voltage test
According to IEC 60255-5
•
Test voltage
5 kV, unipolar impulses, waveform 1.2/50
µ
s,
source energy 0.5 J
Insulation resistance
measurements
According to IEC 60255-5
•
Isolation resistance
> 100 M
Ω
, 500 V dc
Mechanical tests
Vibration tests (sinusoidal)
According to IEC 60255-21-1 class I
Shock and bump test
According to IEC 60255-21-2 class I
Table 4.2.3-12 Data communication
Rear interface, connector X2.2
•
RS-485 connection for fibre-optic interface module RER 103
•
SPA-bus
protocol
•
4.8 or 9.6 kbps
Front panel
•
Optical RS-232 connection for opto-cable
•
SPA-bus
protocol
•
4.8 or 9.6 kbps
Содержание REJ 523
Страница 64: ...REJ 523 Technical Reference Manual ABB Substation Automation Products and Systems MRS750940 MUM 64 ...
Страница 65: ...ABB Substation Automation Products and Systems Technical Reference Manual REJ 523 1MRS750940 MUM 65 ...
Страница 66: ...REJ 523 Technical Reference Manual ABB Substation Automation Products and Systems MRS750940 MUM 66 ...
Страница 67: ......