Description
Para-
meter
R/W
Value
Internal fault code
V169
R
0...255
SPA address of the relay
V200
R, W
1...254
Data transfer rate, kbps
V201
R, W
4.8 or 9.6
Rear communication
V202
W
1=communication to rear
connector
Relay serial number
V230
R
ERxxxxxx
CPU serial number
V231
R
MRxxxxxx
Hardware number
V232
R
1MRS090414-BAA
Test date
V233
R
YYYYMMDD
Software number
V234
R
1MRS118012
Software revision
V235
R
A...Z
Date reading and setting
(RED 500 format)
V250
R, W
YY-MM-DD
Time reading and setting
(RED 500 format)
V251
R, W
HH.MM; SS.mss
Reading of event register
L
R
Time, channel number and
event code
Re-reading of event
register
B
R
Time, channel number and
event code
Type designation of the
module
F
R
REJ 523
Reading of module state
data
C
R
0=normal state
1=module been subject to
automatic reset
2=overflow of event
register
3=both events 1 and 2
Resetting of module state
data
C
W
0=resetting
1=reset only E50
2=reset only E51
4=reset all events including
E51, but not E50
Time reading and setting
T
R, W
00.000... 59.999 s
Date and time reading and
setting
D
R, W
YY-MM-DD