ABB Substation Automation
Products and Systems
User’s Guide
REJ 513
1MRS750613-MUM
59
Setting group 2
Variable
Group 2
(R, W, P)
Setting
range
Default
setting
Customer’s
setting
Start current of
stage I>
S81
0.30...5.00 x I
n
0.30 x I
n
Operate time or time
multiplier k of stage I>
S82
0.05...300 s
0.05 s /
0.05
Start current of
stage I>>
S83
0.30...35.0 x I
n
0.30 x I
n
Operate time of
stage I>>
S84
0.04...300 s
0.04 s
Checksum, SGF 1
S85
0...255
0
Checksum, SGF 2
S86
0...255
0
Checksum, SGF 3
S87
0...255
0
Checksum, SGB 1
S88
0...255
0
Checksum, SGR 1
S89
0...255
12
Checksum, SGR 2
S90
0...255
3
Checksum, SGR 3
S91
0...255
12
Checksum, SGR 4
S92
0...255
3
Control parameters
Variable
Parameter
Setting
range
Default
setting
Customer’s
setting
Rated frequency
V133
50 / 60
50
Remote control of
settings
V150
0 / 1
0
Event mask for I>
and I>>
V155
0...255
85
Event mask for output
contacts’ events
V156
0...255
3
Event mask for
disturbance recorder
V157
0 / 1
1
SPA address of the
relay
V200
1...254
1
Data transfer rate
V201
4.8 or 9.6
9.6
Operate time of circuit-
breaker failure
protection
S121
0.10...1.00 s
0.10 s
Содержание REJ 513
Страница 71: ......