ABB Substation Automation
Products and Systems
User’s Guide
REJ 513
1MRS750613-MUM
19
t[s] =
k
I
I
×
>
−
β
α
1
where t = operate time
k = time multiplier
I = phase current value
I> = set current value.
Table 2.1.3.3-1 The values of constants
α
and
β
Time/current curve group
α
β
Normal inverse
0.02
0.14
Very inverse
1.0
13.5
Extremely inverse
2.0
80.0
Long-time inverse
1.0
120
The standard BS 142.1966 defines the normal current range to be 2...20 times the
setting value. In addition, the relay has to start at the latest when the current exceeds
the setting value 1.3 times if the time/current characteristic is normal inverse, very
inverse or extremely inverse. For the long-time inverse characteristic the normal
current range is specified to be 2...7 times the setting, and the relay is to start when
the current exceeds the setting value 1.1 times.
Table 2.1.3.3-2 The operate time tolerances specified by the standard
I/I>
Normal
Very
Extremely
Long time
2
2,22E
2,34E
2,44E
2,34E
5
1,13E
1,26E
1,48E
1,26E
7
-
-
-
1,00E
10
1,01E
1,01E
1,02E
-
20
1,00E
1,00E
1,00E
-
E = accuracy in per cent; - = not specified
In the normal current ranges, specified above, the inverse-time stage of the
overcurrent relay fulfils the tolerance requirements of class 5 at all degrees of
inversity.
The time/current characteristics according to the IEC and BS standards are illustrated
in figures 2.1.3.3-1…2.1.3.3-4.