REJ 513
User’s Guide
ABB Substation Automation
Products and Systems
1MRS750613-MUM
54
Table 2.2.2-3 Energizing inputs
Rated frequency
50/60 Hz
±
5 Hz
Rated current I
n
1 A
5 A
Thermal withstand capability
•
continuously
4 A
20 A
•
for 1 s
100 A
500 A
Dynamic current withstand
•
half-wave value
250 A
1250 A
Input impedance
< 100 m
Ω
< 20 m
Ω
Table 2.2.2-4 Measuring range
Measured currents on phases L1, L2 and L3 as multiples of
the rated currents of the energizing inputs
0…50 x I
n
Table 2.2.2-5 Binary input
•
Operating range
18…265 V dc
•
Rated voltage
24/48/60/110/220 V dc
•
Current drain
~ 2…25 mA
•
Power consumption
< 0.8 W
Table 2.2.2-6 Signal outputs (SO1, SO2) and self-supervision output (IRF)
•
Rated voltage
250 V ac/dc
•
Continuous carry
5 A
•
Make and carry for 3.0 s
8 A
•
Make and carry for 0.5 s
10 A
•
Breaking capacity when the control circuit time-
constant L/R < 40 ms, at 48/110/220 V dc
1 A / 0.25 A / 0.15 A
•
Minimum contact load
100 mA at 24 V ac/dc