ABB Substation Automation
Products and Systems
User’s Guide
REJ 513
1MRS750613-MUM
49
Input and output signals
The measured currents and the status of the binary input signal can be read (R) with
parameters I1...I4. When the value of parameter I4 is 1, the binary input is energized.
Table 2.1.7.3-9 Inputs
Information
Parameters (R)
Value
Current measured on phase L1
I1
0...50 x I
n
Current measured on phase L2
I2
0...50 x I
n
Current measured on phase L3
I3
0...50 x I
n
Binary input signal BI
I4
0 or 1
Each protection stage has its logical output signal. These signals can be read (R) with
parameters O1...O4. The state of the output contacts can be read (R) or changed (W)
with parameters O5...O8. Functions indicated by parameters O1…O8 are recorded
and they can be read with parameters O21…O28.
Table 2.1.7.3-10 Output signals
Status of the protection
stages
State of stage
(R)
Recorded
functions (R)
Value
Starting of stage I>
O1
O21
0 or 1
Tripping of stage I>
O2
O22
0 or 1
Starting of stage I>>
O3
O23
0 or 1
Tripping of stage I>>
O4
O24
0 or 1
Table 2.1.7.3-11 Outputs
Operation of output
contacts
State of output
(R,W,P)
Recorded
functions (R)
Value
Output PO1
O5
O25
0 or 1
Output PO2
O6
O26
0 or 1
Output SO1
O7
O27
0 or 1
Output SO2
O8
O28
0 or 1
Enable of output
contacts PO1, PO2,
SO1 and SO2
O41
-
0 or 1