ABB Substation Automation
Products and Systems
User’s Guide
REJ 513
1MRS750613-MUM
47
Control parameters
Table 2.1.7.3-8 Control parameters
Description
Para-
meter
R/W
Value
Resetting of output
contacts with the latching
feature
V101
W
1=reset
Resetting of registers and
output contacts with the
latching feature
V102
W
1=reset
Rated frequency
V133
R,W(P)
50=50 Hz
60=60 Hz
Remote control of settings
V150
R,W
0=setting group 1
1=setting group 2
Event mask for I> and I>>
V155
R,W
0...255, see Event codes
Event mask for output
contacts’ events
V156
R,W
0...255, see Event codes
Event mask for
disturbance recorder
V157
R,W
0 / 1, see Event codes
Entering the password for
settings
V160
W
1...999
Changing the password or
reinstating password
protection
V161
W(P)
1...999
Activating the self-
supervision READY LED
V165
W
0=normal operation
1=self-supervision READY
LED blinking
LED test for start and trip
indicators
V166
W(P)
0=start and trip LEDs off
1=trip LED on, start LED
off
2= start LED on, trip LED
off
3=start and trip LEDs on
Default settings
V167
W(P)
2=Restore factory settings
Table continues on next page.