REJ 513
User’s Guide
ABB Substation Automation
Products and Systems
1MRS750613-MUM
30
Table 2.1.3.4-3 SGF2
Switch
Function
Default
setting
SGF2/1
Automatic doubling of the start current of stage I>>.
When the switch is in position 1, the set value for the
stage is automatically doubled at start-up.
0
SGF2/2
Inverse-time operation of stage I> inhibited by the starting
of stage I>>.
When the switch is in position 1, the inverse-time
operation is inhibited.
0
SGF2/3
Inhibition of the operation of stage I>>.
When the switch is in position 1, the operation of stage
I>> is inhibited.
0
SGF2/4
The operation mode of the start indicator of stage I>.
When the switch is in position 0, the start indicator
automatically resets once the fault disappears.
0
SGF2/5
The operation mode of the start indicator of stage I>>.
When the switch is in position 0, the start indicator
automatically resets once the fault disappears.
0
SGF2/6
Not in use.
0
SGF2/7
Not in use.
0
SGF2/8
Not in use.
0
Σ
SGF2
0
Table 2.1.3.4-4 SGF3
SGF3/1
SGF3/2
SGF3/3
SGF3/4
SGF3/5
SGF3/6
SGF3/7
SGF3/8
Operation
0
0
0
0
0
0
-
-
Definite-time
1)
1
0
0
0
0
0
-
-
Extremely inverse
0
1
0
0
0
0
-
-
Very inverse
0
0
1
0
0
0
-
-
Normal inverse
0
0
0
1
0
0
-
-
Long-time inverse
0
0
0
0
1
0
-
-
RI-type
characteristic
0
0
0
0
0
1
-
-
RD-type
characteristic
1)
Default setting