ABB Substation Automation
Products and Systems
User’s Guide
REJ 513
1MRS750613-MUM
39
Table 2.1.7.2-2 Event codes E1…E8
Code
Event
Weighting
factor
Default value
E1
Starting of stage I>
1
1
E2
Starting of stage I> reset
2
0
E3
Tripping of stage I>
4
1
E4
Tripping of stage I> reset
8
0
E5
Starting of stage I>>
16
1
E6
Starting of stage I>> reset
32
0
E7
Tripping of stage I>>
64
1
E8
Tripping of stage I>> reset
128
0
Default value of event mask V155
85
Table 2.1.7.2-3 Event codes E9…E16
Code
Event
Weighting
factor
Default value
E9
PO1 activated
1
1
E10
PO1 reset
2
1
E11
PO2 activated
4
0
E12
PO2 reset
8
0
E13
SO1 activated
16
0
E14
SO1 reset
32
0
E15
SO2 activated
64
0
E16
SO2 reset
128
0
Default value of event mask V156
3
Table 2.1.7.2-4 Event code E31
Code
Event
Weighting
factor
Default value
E31
Disturbance recorder triggered
and finished recording
1
1
Default value of event mask V157
1
Содержание REJ 513
Страница 71: ......