42 Planning the installation
Checking solar array and inverter compatibility
Check that:
• Solar modules and DC cables used in the system are Protection Class II certified
(double insulated).
• Solar modules used in the system do not require grounding of DC+ or DC-
terminals.
• Solar modules used in the system are all of the same type and that they all have
IEC 61730 Class A rating.
• Solar strings to be connected to the inverter all have an equal configuration.
• Solar string and array maximum short circuit currents and open circuit voltages
match the rated values of the inverter under local ambient conditions.
• Solar array operating voltage range lies between the limits of the maximum power
point tracking (MPPT) voltage range.
• The inverter’s standard 12A string fuse rating is adequate and compatible with the
solar array design and installation materials. Change the string fuses to a lower or
higher current rating if necessary to provide adequate system protection and
functionality. See section
Warning messages
on page
107
.
Process for selecting the string fuse nominal current rating
I
FN
• Define the nominal short circuit current
I
SC
rating from the data sheet of the
relevant solar module.
• Define the maximum allowed series fuse rating or reverse current rating
I
R
from
the data sheet of the relevant solar module.
• Define the conductor current carrying capacity
I
C
of the used string cable type
under the planned installation conditions. See section
Selecting the power cables
on page
37
.
• Correct fuse current rating under planned installation conditions:
I
FN
> 1.56 ×
I
SC
I
FN
≤
I
R
or if
I
R
not specified in module data sheet
I
FN
< 2 ×
I
SC
I
FN
≤
I
C
Implementing short-circuit and thermal overload protection
Protecting the inverter and AC output cable from short-circuits
The inverter has an integrated automatic AC overcurrent trip function which limits
inverter damage if there is, for example, an AC side short-circuit or other overcurrent
event. Install an external circuit breaker at the distribution board to protect the AC
cable according to local regulations, appropriate AC line voltage and the rated current
of the inverter.
Содержание PVS300
Страница 1: ...ABB solar inverters Product manual PVS300 string inverters ...
Страница 4: ......
Страница 9: ...Table of contents 9 Further information ...
Страница 10: ...10 Table of contents ...
Страница 34: ...34 Operation basics and hardware description ...
Страница 48: ...48 Planning the installation ...
Страница 76: ...76 Installation checklist ...
Страница 110: ...110 Troubleshooting ...
Страница 120: ...120 Technical data ...
Страница 122: ...122 Dimension drawing 3AUA0000094904 ...
Страница 123: ...Dimension drawing 123 Required clearances for cooling ...
Страница 124: ...124 Dimension drawing ...
Страница 126: ...126 Navigation map The navigation map ...
Страница 127: ...Navigation map 127 ...
Страница 128: ...128 Navigation map ...
Страница 130: ...3AUA0000096321 Rev B EN EFFECTIVE 2013 03 14 Contact us www abb com solar ...