102 Troubleshooting
Fault messages and their corrective actions
Fault
message
ID code
Fault message
description
Causes of fault and corrective actions
1
Overcurrent
The inverter has performed an overcurrent trip and has
disconnected from the grid. Possible causes for an overcurrent
peak are an AC side short-circuit, sudden AC side disturbance or
inverter malfunction.
Check if the AC side circuit breaker for inverter output protection
at the electrical distribution board has also tripped. If it has, the
electrical system should be checked by an electrician. If it has not,
try to reset the fault and restart the inverter.
2
DC bus
overvoltage
The inverter has diagnosed high DC voltage. The inverter might
be damaged.
Check and record the DC voltage reading from the Technical
information page.
If the fault is active but the DC voltage reading is under 900 VDC,
try to reset the fault and restart the inverter.
If the DC voltage reading is over 900 V, turn the DC switch to ‘0’
position. The DC voltage shown in the Technical Information view
should start to decrease.
Always inform your system supplier about DC bus overvoltage
faults because excessive DC voltage levels can damage the
inverter.
4
DC cap
overvoltage
The inverter has diagnosed excessive DC capacitor voltage
caused by imbalance between the upper and lower capacitors.
Check and record the DC voltage reading from the Technical
information page.
If the fault is active but the DC voltage reading is under 900 VDC,
try to reset the fault and restart the inverter.
Содержание PVS300
Страница 1: ...ABB solar inverters Product manual PVS300 string inverters ...
Страница 4: ......
Страница 9: ...Table of contents 9 Further information ...
Страница 10: ...10 Table of contents ...
Страница 34: ...34 Operation basics and hardware description ...
Страница 48: ...48 Planning the installation ...
Страница 76: ...76 Installation checklist ...
Страница 110: ...110 Troubleshooting ...
Страница 120: ...120 Technical data ...
Страница 122: ...122 Dimension drawing 3AUA0000094904 ...
Страница 123: ...Dimension drawing 123 Required clearances for cooling ...
Страница 124: ...124 Dimension drawing ...
Страница 126: ...126 Navigation map The navigation map ...
Страница 127: ...Navigation map 127 ...
Страница 128: ...128 Navigation map ...
Страница 130: ...3AUA0000096321 Rev B EN EFFECTIVE 2013 03 14 Contact us www abb com solar ...