38 Planning the installation
Recommended AC output power cable types
The power cable types that can be used for the inverter AC output are shown below.
Shielded cable with line and neutral conductors and a concentric
PE conductor as shield. The shield must meet the PE conductor
cross section requirements, see
General rules
on page
37
. Check
with local / state / country electrical codes for allowance.
Shielded cable with line and neutral conductors and a concentric
PE conductor as shield. A separate PE conductor is required if the
shield does not meet the cross section requirements, see
General
rules
on page
37
.
Double insulated cable with line, neutral and PE conductors. A
separate PE conductor is required if the shield does not meet the
cross section requirements, see
General rules
on page
37
.
1
Insulation jacket
2
Copper wire screen
3
Cable cores
1
2
3
Содержание PVS300
Страница 1: ...ABB solar inverters Product manual PVS300 string inverters ...
Страница 4: ......
Страница 9: ...Table of contents 9 Further information ...
Страница 10: ...10 Table of contents ...
Страница 34: ...34 Operation basics and hardware description ...
Страница 48: ...48 Planning the installation ...
Страница 76: ...76 Installation checklist ...
Страница 110: ...110 Troubleshooting ...
Страница 120: ...120 Technical data ...
Страница 122: ...122 Dimension drawing 3AUA0000094904 ...
Страница 123: ...Dimension drawing 123 Required clearances for cooling ...
Страница 124: ...124 Dimension drawing ...
Страница 126: ...126 Navigation map The navigation map ...
Страница 127: ...Navigation map 127 ...
Страница 128: ...128 Navigation map ...
Страница 130: ...3AUA0000096321 Rev B EN EFFECTIVE 2013 03 14 Contact us www abb com solar ...