76
Functions
| Installation and commissioning manual | 1SFC132081M0201
7.2 Voltage
ramp
When using the Voltage ramp, the voltage increases
linearly from Initial start level to full voltage during start,
and decreases linearly from the Step down level to Stop
end voltage level during stop, see
Figure 7.1.
The torque not always follows the voltage curve, because
the torque is also subject to the current. This has the
effect that the torque does not increase or decrease
linearly.
7.2.1
Voltage start ramp
When the Softstarter receives a start signal, the
Softstarter quickly increases the voltage to the Start
ramp initial level. The Softstarter then controls the output
voltage in a start ramp.
When the output voltage comes at Top of ramp, the
Softstarter closes the bypass, see
Figure 7.2.
To come at Top of ramp these conditions are necessary:
• The Start ramp time passed, i.e. 100% output voltage.
• The current is below 1.2 × nominal motor current.
The Start ramp time is the time it takes to go from Start
ramp initial level to full voltage. The time to come at Top
of ramp can be longer than the set Voltage ramp time,
because this is subject to the current.
If the motor starts with a very heavy load, the start ramp
time can be longer than usual.
Example: If the Start ramp time is set to 2 seconds and
the motor starts a heavy load, this can cause the output
current to not go below the set 120% of nominal motor
current when the pre-set start ramp time is reached.
Configuration of the Voltage start ramp with these
parameters:
Parameter
Description
Setting range
Default value
02.01 Start mode
Set the Start mode to Voltage ramp.
Voltage ramp,
Torque ramp,
Full voltage ramp
Voltage ramp
02.03 Start ramp Initial level
Set the voltage level from where the start ramp initiates
10 ... 99%
30%
02.04 Start ramp time
Set the effective time it takes for the voltage to reach
100%.
1 ... 120 s
10 s
Figure 7.1
Start and stop ramp
1SFC132081M0201
U
Time
Start ramp
Stop ramp
Figure 7.2
Voltage start ramp
U
Time
Start ramp time
Start ramp initial level
Top of ramp
Nominal voltage 100 %
1SFC132081M0201
7
Содержание PSTX Series
Страница 1: ...1SFC132081M0201 Softstarters Type PSTX30 PSTX1250 Installation and commissioning manual...
Страница 4: ......
Страница 6: ......
Страница 10: ...10 Introduction Installation and commissioning manual 1SFC132081M0201 1...
Страница 16: ...16 Quick start Installation and commissioning manual 1SFC132081M0201 2...
Страница 29: ...1SFC132081M0201 Installation and commissioning manual Description 29 3...
Страница 30: ...30 Description Installation and commissioning manual 1SFC132081M0201 3...
Страница 36: ...36 Installation Installation and commissioning manual 1SFC132081M0201 4...
Страница 50: ...50 Connection Installation and commissioning manual 1SFC132081M0201 6...
Страница 72: ...72 Human machine interface HMI Installation and commissioning manual 1SFC132081M0201 6...
Страница 143: ...1SFC132081M0201 Installation and commissioning manual Functions 143 7...
Страница 144: ...144 Functions Installation and commissioning manual 1SFC132081M0201 7...
Страница 148: ...148 Communication Installation and commissioning manual 1SFC132081M0201 8...
Страница 156: ...156 Maintenance Installation and commissioning manual 1SFC132081M0201 9...
Страница 168: ...168 Troubleshooting Installation and commissioning manual 1SFC132081M0201 10...
Страница 176: ...176 Wiring and application diagrams Installation and commissioning manual 1SFC132081M0201 11...
Страница 181: ...1SFC132081M0201 Installation and commissioning manual Third party licenses 181 12...
Страница 183: ...1SFC132081M0201 Installation and commissioning manual Revision 183 13...
Страница 187: ...1SFC132081M0201 Installation and commissioning manual Index 187 14...