1SFC132081M0201 | Installation and commissioning manual |
Functions
125
7.20.5 Step down level
When the Softstarter receives a stop signal the Softstarter
first decreases the output voltage to the motor in a quick
stop ramp, from full voltage down to set Step down
voltage level. Then the Softstarter controls the output
voltage in a stop ramp.
You can adjust the step down level for torque control.
When using voltage ramp, set it to 80%. It can be
necessary to adjust the step down level if the load is too
high or too low.
Step down level has these parameters:
Parameter
Description
Setting range
Default value
28.05 Step down level
Set the level from where the stop
ramp initiates.
10% ... 100%
80%
7.20.6 System
mode
Select between:
• Normal
mode
• Demo
mode
• Small motor mode
Normal mode
Normal mode is the default setting and is used in all
situations except the ones given below.
Demo mode
Demo is used mainly for training purposes to simulate a
load condition without having the Softstarter connected
to main power.
WARNING
When the Softstarter is connected to a motor, do
not select demo mode, a direct start will occur.
Small motor mode
Small motor mode is used for basic testing purposes,
when using a smaller motor than the PSTX is specified
for. The Softstarter is able to start the motor, but some
functions and protections are disabled.
INFORMATION
The current through the Softstarter has to be at
least 3A when using small motor mode.
System mode has these parameters:
Parameter
Description
Setting range
Default value
28.41 System mode
Sets the run mode.
Normal, Demo, small
motor
Normal
7.20.7 TOR relay delay time
Set the delay time from Top Of Ramp until the Top Of
Ramp relay is on
TOR relay delay time has these parameters:
Parameter
Description
Setting range
Default value
28.03 TOR relay delay time
Set the delay time from Top Of Ramp until
the Top Of Ramp relay is on
0.0 ... 300.0 s
0.0 s
7
Содержание PSTX Series
Страница 1: ...1SFC132081M0201 Softstarters Type PSTX30 PSTX1250 Installation and commissioning manual...
Страница 4: ......
Страница 6: ......
Страница 10: ...10 Introduction Installation and commissioning manual 1SFC132081M0201 1...
Страница 16: ...16 Quick start Installation and commissioning manual 1SFC132081M0201 2...
Страница 29: ...1SFC132081M0201 Installation and commissioning manual Description 29 3...
Страница 30: ...30 Description Installation and commissioning manual 1SFC132081M0201 3...
Страница 36: ...36 Installation Installation and commissioning manual 1SFC132081M0201 4...
Страница 50: ...50 Connection Installation and commissioning manual 1SFC132081M0201 6...
Страница 72: ...72 Human machine interface HMI Installation and commissioning manual 1SFC132081M0201 6...
Страница 143: ...1SFC132081M0201 Installation and commissioning manual Functions 143 7...
Страница 144: ...144 Functions Installation and commissioning manual 1SFC132081M0201 7...
Страница 148: ...148 Communication Installation and commissioning manual 1SFC132081M0201 8...
Страница 156: ...156 Maintenance Installation and commissioning manual 1SFC132081M0201 9...
Страница 168: ...168 Troubleshooting Installation and commissioning manual 1SFC132081M0201 10...
Страница 176: ...176 Wiring and application diagrams Installation and commissioning manual 1SFC132081M0201 11...
Страница 181: ...1SFC132081M0201 Installation and commissioning manual Third party licenses 181 12...
Страница 183: ...1SFC132081M0201 Installation and commissioning manual Revision 183 13...
Страница 187: ...1SFC132081M0201 Installation and commissioning manual Index 187 14...