1SFC132081M0201 | Installation and commissioning manual |
Troubleshooting
163
10.4 Protection indication shown on screen
For a description of the protections, see
chapter
7.17 Protections
.
Table 2
Protection indication
Status
Possible cause
Solution
Electronic overload
The motor got an overload
because the current is too high
during some time. (The load on the
motor shaft is too high)
In Line / Inside Delta
At start
•
Examine start conditions and EOL settings.
•
Examine and correct the reason for the overload.
•
Make sure that Current limit level is not set too low.
•
Make sure that the ramp time for start is not too long.
•
Make sure that correct overload class is used.
•
Make sure that parameter Setting Ie is correct.
Continuous run
•
Do a check of the rating of the plate for Ie.
•
Do a check of the operation voltage.
•
Use a motor with more power, and
•
a Softstarter rated for higher current.
•
Examine and correct the reason for the
• overload.
•
Make sure that correct EOL Class is used.
Locked rotor
The motor does not run easily.
A possible cause is a damaged
bearing or a load stock.
•
Examine the bearings of the motor and load.
•
Make sure that the load runs easily.
Phase reversal
The phase sequence is not
correct. Current imbalance
between the phases.
•
Change the phase sequence on the line side to (L1-
L2-L3).
•
Start the motor again and do a check of the main
currents and voltage.
Current imbalance
Current imbalance between the
phases.
•
Start the motor again and do a check of the main
currents and voltage.
Current underload
The motor current is below the
specified value.
•
Examine and correct the reason for the underload.
•
Make sure that the motor current parameter (Ie) is set
correctly.
User defined protection
With the programmable digital
input and an external device/
sensor the user can use his own
specified protection.
•
Set the programmable input signal to inactive state
before you reset the protection event.
Ground fault
Equipment protection. In a
symmetrical 3-phase system, the
sum of the instantaneous line
currents is equal to zero. Ground
fault indicates if the sum differs
more than the specified value. This
can indicate a serious condition of
the motor.
•
Examine motor cables.
•
Examine the motor.
Overvoltage
The main voltage is too high
•
Do a check of the main voltage.
Under voltage
The main voltage is too low.
•
Do a check of the main voltage.
Voltage imbalance
Voltage imbalance between the
phases.
•
Do a check of the main voltage and start the motor
again.
External thermal sensor
- PTC protection
- PT100 protection
The external thermal sensor
detected a temperature higher
than the trip level in the motor or
PT100.
•
Make sure that the PTC or PT100 circuit is closed and
that the inputs are connected.
•
Examine and correct the reason for the high
temperature.
•
Wait for the temperature of the motor to decrease
sufficiently and start again.
10
Содержание PSTX Series
Страница 1: ...1SFC132081M0201 Softstarters Type PSTX30 PSTX1250 Installation and commissioning manual...
Страница 4: ......
Страница 6: ......
Страница 10: ...10 Introduction Installation and commissioning manual 1SFC132081M0201 1...
Страница 16: ...16 Quick start Installation and commissioning manual 1SFC132081M0201 2...
Страница 29: ...1SFC132081M0201 Installation and commissioning manual Description 29 3...
Страница 30: ...30 Description Installation and commissioning manual 1SFC132081M0201 3...
Страница 36: ...36 Installation Installation and commissioning manual 1SFC132081M0201 4...
Страница 50: ...50 Connection Installation and commissioning manual 1SFC132081M0201 6...
Страница 72: ...72 Human machine interface HMI Installation and commissioning manual 1SFC132081M0201 6...
Страница 143: ...1SFC132081M0201 Installation and commissioning manual Functions 143 7...
Страница 144: ...144 Functions Installation and commissioning manual 1SFC132081M0201 7...
Страница 148: ...148 Communication Installation and commissioning manual 1SFC132081M0201 8...
Страница 156: ...156 Maintenance Installation and commissioning manual 1SFC132081M0201 9...
Страница 168: ...168 Troubleshooting Installation and commissioning manual 1SFC132081M0201 10...
Страница 176: ...176 Wiring and application diagrams Installation and commissioning manual 1SFC132081M0201 11...
Страница 181: ...1SFC132081M0201 Installation and commissioning manual Third party licenses 181 12...
Страница 183: ...1SFC132081M0201 Installation and commissioning manual Revision 183 13...
Страница 187: ...1SFC132081M0201 Installation and commissioning manual Index 187 14...