22
Description
| Installation and commissioning manual | 1SFC132081M0201
3.2 Technical
data
3.2.1 General
Table 3
General
General data
Description
24 V output
24 V ± 5% Max 250 mA
Rated insulation voltage,
Ui
600 V / 690 V
Rated operation voltage,
Ue
208-600 / 690 V, 50 / 60 Hz
Rated supply voltage,Us
100-250 V, 50 / 60 Hz
Voltage tolerance
+10% to -15%
Rated frequency
50 / 60 Hz
Frequency tolerances
± 10%
Rated impulse withstand
voltage
6 kV Operation circuit
4 kV Control and supply circuit
Relay outputs
3 programmable
Number of controlled
phases
3
Inputs
Start, stop, 3 programmable inputs
(Digital I/O: In0, In1, In2), temperature
sensor input.
Outputs
Relay outputs: K4 K5 K6.
Output relay
performance
250 V AC, Ith = 5A, Ie = 1.5A (AC-15)
Analog output
4-20 mA, 0-20 mA, 0-10 V, 0-10 mA
PTC input
2825 ohm ± 20% switch off resistance
1200 ohm ± 20% switch on resistance
Cooling system
Fan
Recommended fuse
Control supply circuit
6 A Delayed
MCB use C characteristics
Communication
3 Fieldbus ports, Extension I/O
Communication
protocols
DeviceNet / Profibus DP / Modbus /
EtherNET/IP / Modbus TCP/ Profinet
3.2.2
Technical data for external keypad
Table 4
Technical data for external keypad
Display
Display type
Status indicating LEDs
Ready:
Green
Run:
Green
Protection:
Yellow
Fault:
Red
Ambient temperature
Storage:
-25 °C to +70 °C (-13 °F
to 158 °F)
Operation:
-25 °C to +60 °C
(-13 °F to 140 °F)
Degree of protection
IP66
UL approval
Type 1
Type 4X
Type 12
Marine approvals
Speak to your ABB sales office
3.2.3 Semi-conductor
fuses
WARNING!
Semiconductor fuses must be used to keep the
warranty on the thyristors.
INFORMATION
To achieve a type 2 coordination, semiconductor
fuses must be used.
Table 5
Fuses ratings and power losses
Current
range
Max
power
loss at
rated I
e
Max fuse raiting - main
circuit
1) 2)
Bussmann fuses, DIN43 620
(Knife)
Power
require-
ments
supply
circuit
Holding
(VA) /
Type
A
W
A
Type
Size
Pull-in
(VA)
PSTX30
9.0...30.0
0.8
100
170M1567
000
49/51
PSTX37
11.1...37.0
1.2
125
170M1568
000
49/51
PSTX45
13.5...45.0
1.8
160
170M1569
000
49/51
PSTX60
18.0...60.0
3.2
160
170M1569
000
49/51
PSTX72
21.6...72.0
4.7
250
170M1571
000
49/51
PSTX85
22.5...85.0
6.5
315
170M1572
000
49/51
PSTX105
31.8...106.0
10
400
170M3819
1*
49/51
PSTX142
42.9...143.0
18
500
170M5810
2
49/53
PSTX170
51.3...171.0
26
630
170M5812
2
49/53
PSTX210
63.0...210.0
48
630
170M5812
2
56/276
PSTX250
75.0...250.0
68
700
170M5813
2
56/276
PSTX300
90.0...300.0
97
800
170M6812
3
56/276
PSTX370
111.0...370.0
148
900
170M6813
3
56/276
PSTX470
141.0...470.0
99
900
170M6813
3
67/434
PSTX570
171.0...570.0
146
1000
170M6814
3
67/434
PSTX720
216.0...720.0
78
1250
170M8554
3
61/929
PSTX840
252.0...840.0
106
1500
170M6018
3
61/929
PSTX1050
3)
315.0...1050.0
165
1800
170M6020
3
68/929
PSTX1250
3) 4)
375.0...1250.0
234
2000
170M6021
3
68/929
1)
For the supply circuit 6 A delayed, for MCB use C characteristics.
2)
For inside delta connection the fuses shall be placed inside the delta. Contact ABB for
more information.
3)
170M6019 with fuse rating 1600 A should be used for 690 V version.
4)
For 690 V version, Bussmann fuses are only available for motors with rated current up
to 1150 A.
You can find more detailed information at:
http://applications.it.abb.com/SOC/
3.2.4 Weights
Table 6
Weights
Type
Weight in kg
Weight in lbs
PSTX30...105
6,1
13,5
PSTX142...170
9,6
21,2
PSTX210...370
12,7
27,9
PSTX470
25.5
55.1
PSTX570
27.5
59.5
PSTX720 ...840
46.2
101.4
PSTX1050
64.5
141.1
PSTX1250
65
143.3
3
Содержание PSTX Series
Страница 1: ...1SFC132081M0201 Softstarters Type PSTX30 PSTX1250 Installation and commissioning manual...
Страница 4: ......
Страница 6: ......
Страница 10: ...10 Introduction Installation and commissioning manual 1SFC132081M0201 1...
Страница 16: ...16 Quick start Installation and commissioning manual 1SFC132081M0201 2...
Страница 29: ...1SFC132081M0201 Installation and commissioning manual Description 29 3...
Страница 30: ...30 Description Installation and commissioning manual 1SFC132081M0201 3...
Страница 36: ...36 Installation Installation and commissioning manual 1SFC132081M0201 4...
Страница 50: ...50 Connection Installation and commissioning manual 1SFC132081M0201 6...
Страница 72: ...72 Human machine interface HMI Installation and commissioning manual 1SFC132081M0201 6...
Страница 143: ...1SFC132081M0201 Installation and commissioning manual Functions 143 7...
Страница 144: ...144 Functions Installation and commissioning manual 1SFC132081M0201 7...
Страница 148: ...148 Communication Installation and commissioning manual 1SFC132081M0201 8...
Страница 156: ...156 Maintenance Installation and commissioning manual 1SFC132081M0201 9...
Страница 168: ...168 Troubleshooting Installation and commissioning manual 1SFC132081M0201 10...
Страница 176: ...176 Wiring and application diagrams Installation and commissioning manual 1SFC132081M0201 11...
Страница 181: ...1SFC132081M0201 Installation and commissioning manual Third party licenses 181 12...
Страница 183: ...1SFC132081M0201 Installation and commissioning manual Revision 183 13...
Страница 187: ...1SFC132081M0201 Installation and commissioning manual Index 187 14...