![ABB PowerCube PB/F Скачать руководство пользователя страница 18](http://html.mh-extra.com/html/abb/powercube-pb-f/powercube-pb-f_installation-and-service-instructions-manual_2838039018.webp)
16
Tab. 4 - Interruttori estraibili Vmax
Table 4 - Withdrawable Vmax circuit-breakers
kV
Isc
Icw
W=600
W=750
W=750
W=750
Tipo di apparecchio
PowerCube
(kA)
(kA)
p=150
p=210
p=210
p=210
Type of apparatus
3 s
u/l=205
u/l=310
u/l=310
u/l=310
H=260
H=280
H=280
H=325
ø=35
ø=35
ø=79
ø=35
12-17,5
16
16
630
Vmax/W 12.06.16 p150
Vmax/W 17.06.16 p150 *
PB1/F
20
20
630
Vmax/W 12.06.20 p150
Vmax/W 17.06.20 p150 *
25
25
630
Vmax/W 12.06.25 p150
Vmax/W 17.06.25 p150 *
31,5
31,5
630
Vmax/W 12.06.32 p150
Vmax/W 17.06.32 p150 *
16
16
1250
Vmax/W 12.12.16 p150
Vmax/W 17.12.16 p150 *
20
20
1250
Vmax/W 12.12.20 p150
Vmax/W 17.12.20 p150 *
25
25
1250
Vmax/W 12.12.25 p150
Vmax/W 17.12.25 p150 *
31,5
31,5
1250
Vmax/W 12.12.32 p150
Vmax/W 17.12.32 p150 *
Apparecchio abbinabile
alla parte fissa
Apparatus which can be
combined with the fixed part
W = Larghezza parte fissa.
P = Interasse orizzontale tra i poli dell’interruttore.
u/l = Distanza tra terminale superiore e inferiore.
H
= Distanza tra terminale inferiore e terra.
Ø = Diametro dei contatti presenti nel monoblocco delle unità PowerCube
tipo PB.
*
= Per la disponibilità chiedere ad ABB.
W = Width of fixed part
P = Horizontal centre distance between circuit-breaker poles.
u/l = Distance between top and bottom terminal.
H
= Distance between bottom terminal and earth.
Ø = Diameter of the contacts in the PB type PowerCube unit monobloc.
*
= For availability ask ABB.
Corrente nominale dell’apparecchio
inserito nella parte fissa
Rated current of the apparatus racked
into the fixed part
Tab. 5 - Contattori estraibili V-Contact
Table 5 - Withdrawable V-Contact contactors
kV
Isc
Icw
W=600
Contattore
PowerCube
(kA)
(kAx1s)
p=150
Contactor
(1)
u/l=205
H=260
ø=35
7,2
16
6
400 (2)
V7/W
PB 1/F
20
6
400 (2)
VSC7/P
25
6
400 (2)
31,5
6
400 (2)
12
16
6
400 (2)
V12/W
20
6
400 (2)
VSC12/P
25
6
400 (2)
31,5
6
400 (2)
Corrente nominale dei contattori
V-Contact
(A - 40 °C)
Rated current of the
V-Contact
contactors (A - 40 °C)
(1) Garantita impiegando fusibili adatti.
(2) La corrente nominale è soggetta a declassamento in funzione della corrente
nominale dei fusibili.
(1) Guaranteed using suitable fuses.
(2) The rated current is subject to derating according to the rated current of the
fuses.
Содержание PowerCube PB/F
Страница 2: ......
Страница 23: ...21 6 2 4 2 6 5 3 1 2 3 4 5 6 7 1 Fig 9a Fig 9b Fig 9 ...
Страница 39: ......