14
kV
Isc
Icw
W=600
W=750
W=750
W=750
Interruttore
PowerCube
(kA)
(kAx3s)
p=150
p=210
p=210
p=210
Circuit-breaker
u/l=205
u/l=310
u/l=310
u/l=310
H=260
H=280
H=280
H=325
ø=35
ø=35
ø=79
ø=35
12 - 17,5
16
16
630
HD4/W 12.06.16 p150
HD4/W 17.06.16 p150
PB 1/F
25
25
630
HD4/W 12.06.25 p150
HD4/W 17.06.25 p150
31,5
31,5
630
HD4/W 12.06.32 p150
HD4/W 17.06.32 p150
16
16
1250
HD4/W 12.12.16 p150
HD4/W 17.12.16 p150
25
25
1250
HD4/W 12.12.25 p150
HD4/W 17.12.25 p150
31,5
31,5
1250
HD4/W 12.12.32 p150
HD4/W 17.12.32 p150
16
16
630
HD4/W 12.06.16 p210
HD4/W 17.06.16 p210
PB 2/F
25
25
630
HD4/W 12.06.25 p210
HD4/W 17.06.25 p210
31,5
31,5
630
HD4/W 12.06.32 p210
HD4/W 17.06.32 p210
16
16
1250
HD4/W 12.12.16 p210
HD4/W 17.12.16 p210
25
25
1250
HD4/W 12.12.25 p210
HD4/W 17.12.25 p210
31,5
31,5
1250
HD4/W 12.12.32 p210
HD4/W 17.12.32 p210
16
16
1600
HD4/W 12.16.16 p210
HD4/W 17.16.16 p210
25
25
1600
HD4/W 12.16.25 p210
HD4/W 17.16.25 p210
31,5
31,5
1600
HD4/W 12.16.32 p210
HD4/W 17.16.32 p210
16
16
2000
HD4/W 12.20.16 p210
HD4/W 17.20.16 p210
25
25
2000
HD4/W 12.20.25 p210
HD4/W 17.20.25 p210
31,5
31,5
2000
HD4/W 12.20.32 p210
HD4/W 17.20.32 p210
24
16
16
630
HD4/W 24.06.16 p210
--
PB 4/F
20
20
630
HD4/W 24.06.20 p210
--
25
25
630
HD4/W 24.06.25 p210
--
16
16
1250
HD4/W 24.12.16 p210
--
20
20
1250
HD4/W 24.12.20 p210
--
25
25
1250
HD4/W 24.12.25 p210
--
Tab. 2 - Interruttori estraibili HD4
W = Larghezza Modulo PowerCube.
P = Interasse orizzontale tra i poli dell’interruttore.
U/L = Distanza tra terminale superiore ed inferiore.
H
= Distanza tra terminale inferiore e terra
Ø = Diametro dei contatti presenti nel monoblocco del modulo PowerCube.
Table 2 - Withdrawable HD4 circuit-breakers
W = Width of PowerCube module.
P = Horizontal centre distance between circuit-breaker poles.
U/L = Distance between top and bottom terminal.
H = Distance between bottom terminal and earth
Ø = Diameter of the contacts in the PowerCube module monobloc.