6.8.2. Auxiliary power supply connection
A customized interface plate with sockets for external signal and auxiliary power supply
cables is installed on the bottom of the CCU.
The auxiliary power supply cables shall be three-phase cables with separate neutral,
separate PE and screen. They will be connected directly to the terminals of an individual
main switch. The screen shall be connected to the grounding rail in each unit.
Figure 6–14 Position of the auxiliary power terminals inside the CCU
1) Auxiliary power UPS
2) Auxiliary power without UPS
3) Auxiliary power 3AC400V without UPS
4) Auxiliary power 3AC400V with UPS