ELECTRICAL INSTALLATION
PRODUCT
PCS6000
DOCUMENT KIND
User manual
DOCUMENT ID.
3BHS600000 E40
REV.
G
LANG.
en
PAGE
6.4.5. Auxiliary and control cables
6.4.5.1. Requirements for auxiliary power cables
To determine the number of cables, see the project-specific wiring diagrams. The wiring
diagrams provide information on the power supply configuration of the drive and the
terminal assignment.
6.4.5.2. Requirements for control cables
6.4.6. Grid side VT and CT measurement cables
Synchronization cables are used in drives with an ARU. A shielded, 3-phase cable without
neutral wire is required for the supply voltage of the synchronization transformer.
NOTICE
Risk of false signals!
▶ DO NOT lay control cables parallel to the power supply cables.
If this cannot be avoided, maintain a minimum distance of 30 cm between the
control and power supply cables.
▶ Cross control and power supply cables at an angle of 90°
Signal type
Cable type
Cross-sectional area
Analog input
Twisted pair(s) - overall shield
0.5 to 2.5 mm
2
Analog output
Twisted pair(s) - overall shield
0.5 to 2.5 mm
2
Digital input
Twisted pair(s) - overall shield
0.5 to 2.5 mm
2
Digital output
Twisted pair(s) - overall shield
0.5 to 2.5 mm
2
Position encoder
(serial interface)
Shielded instrumentation cable,
preferably with twisted pairs
0.5 mm
2
(6 × 2)