PCS100 AVC-20
User Manual
93
10.4.3.3
Description of System Event Notification
Below is an example of a typical email sent to notify the customer of a system event.
From:
Sent:
Saturday, 19 September 2015 4:31 p.m.
To:
Customer <
Subject:
System Event 60001234 fault
surSite Information
Product Information
Date and Time
Highlights
Date
Time
Origin
Event
Cod
e
Description
2015-09-18 16:30:22.00 scm
scm info 1002 scm power up
2015-09-18 16:30:19.00 scm
scm info 1001 scm power supply fail
2015-09-18 16:30:19.00 inverter 1 scm info 1008 presence message seen
2015-09-18 16:30:13.91
system
fault
70
inverter lost
2015-09-18 16:30:13.34 inverter 1 fault
2
desat
2015-09-18 16:30:13.25
inverter 1 warning 4
lvdc psu voltage low
2015-09-18 16:24:39.61
sag end
running ,200 ms, 80%, 75%, 80%, 100%, 100%,
100%
2015-09-18 16:24:39.61
sag end
running,200ms,79%,76%,80%,100%,100%,100%
Note: The table lists the System and PQ events. The event that triggers the email is highlighted in bold text.
Customer:
ABB NZ
Site Name: Napier
Plant Name: Site 1
Note:
AVC connected to Production Line 75
Note:
Feeder 12 O/G
Product type:
PCS100 AVC-20
Model:
Product Rated voltage: 480.00V
Product Rated Power: 1000kVA
Date 2015-09-18
Time 16:30:13.34
Event Code:
2
Event Description: desat
Status of PCS100 AVC-20
Duration of Voltage sag
Utility sag at input to PCS100 AVC-20
PCS100 AVC-20
sag correction