PCS100 AVC-20
User Manual
17
—
3
MODEL DEFINITION
3.1
Type Code
The PCS100 AVC-20 Type Code is given in
the product tables. The Type Code is a
unique code for the specific PCS100 AVC-
20 model and specifies all the components
that are used to construct the model.
From the base code given in the product
tables options can be added to the Type
Code. These options are called plus (+)
codes.
The diagram on the right outlines the
structure of the Type Code:
PCS100-28
400
02B
-
-
- 20 - L
SA
+
PCS100 AVC-20
Rated Voltage
Power Rating
Regulation Performance
Termination Side
Options
Figure 3
-
1: PCS100 AVC
-
20 Type Code
3.1.1
Rated Voltage
This is the rated voltage of the PCS100 AVC-20.
The standard voltage is 400 V.
Other operating voltages (i.e., 380V) are achieved by software settings and setting of an auxiliary transformer
tapping.
3.1.2
Power Rating
Rated power of the system based on the number of power module pairs. Each power module pair operating on
rated voltage provides 500 kVA of power.
Note: Operation at lower than the rated voltage results in less kVA per module pair. Consult the rating tables for
more information.
3.1.3
Regulation Performance
Defines PCS100 AVC-20 regulation performance.
3.1.4
Termination Side
The location of the power terminals (input and output) when viewed from the front of Transformer Enclosure.
3.1.5
Options
Options are described in document 2UCD280000E002 PCS100 AVC-20 Technical Catalogue. Following options are
available:
Availability
Plus Code Option Description
1B
2B
3B
4B, 5B, 6B
Note
BB
Back-to-Back Layout Plan
x
xx
x
SA
Side Aperture
x
x
x
x
Termination palm recommended
for 2B to ensure adequate space for
cable connection