PCS100 AVC-20
User Manual
77
Code
Origin
Type
GDM Info
Description
Recommended Action
195
M
W
CIOB RS485
Timeout
CIOB RS485
Communications timeout
(Modbus).
Repair external RS485 device
202
R, I
W/AB
Transistor
Junction
OverTemp
Rectifier or Inverter
Transistor Junction model
hot.
Check all module fans are
operating properly and
ambient temperature is not
too high.
209
System Info
Reboot
The system is rebooting,
perhaps after a firmware
upgrade.
Info only
210
System Info
Remote
A start, stop or reset
command has been
received from remote
terminal.
No action required
211
System Info
Local
A start, stop or reset
command has been
received from the GDM.
Info only
212
System Info
Automatic
The system has received an
automatic stop command.
Note: This typically occurs
after a reset.
Info only
214
System Info
CanIO
A Mode change command
has been received by
master mux I/O lines
Info only
216
System Info
Modbus
A Mode change command
has been received by a
Modbus connected device
Info only
217
System Info
Factory
webpage
A Mode change command
has been received by the
internal factory web pages
Info only
218
System Info
Remote
webpage
A Mode change command
has been received by the
remote user web pages
info only
219
System Info
Command
Line
A Mode change command
has been received from the
command line
info only
220
System Info
Unknown
source
A Mode change command
has been received from an
unknown source.
Info only
276
R
F
RFI relay
error
RFI relay or driver indicated
a problem.
Power cycle system and if
problem persists contact ABB
service.
283
R
F
Many
contactor
activations
The soft charge contactor
is switching too often.
Replace module.
328
M
W
SCM Comms
lost
The Master has failed to
receive a response to a
status request from the
SCM.
(1) Check the event log for
SCM errors. (2) Check the
power supply to the SCM. (3)
Check VCAN cables and
connections between the
Master and the SCM.