PCS100 AVC-20
User Manual
57
8.3.3
Menu 1 System Electrical
1 System Electrical
The menu contains electrical settings for the product
Parameter:
10 System Current
Function:
Set total rated current of system
–
Line RMS.
Access:
Tech
Range:
0.00 to 1751.95
Units:
Amps (RMS)
Factory Setting:
PCS100 AVC-20 rated current
Parameter:
11 Rectifier Voltage
Function:
Set typical AC (RMS) input voltage of rectifiers.
Access:
Tech
Range:
10 V to 1000 V
Default:
Model dependent
Setting Up:
Preset in the factory
Parameter:
12 Transformer Config
Function:
Selects the Injection transformer terminal configuration
Access:
Tech
Range:
Top Input / Bottom Input
Default:
Top Input
Setting Up:
Preset in the factory
Note:
Top Input = utility supply (input) to top. Bottom Input = utility supply (input) to
bottom. Changing this setting alone does not change the transformer
configuration. Wiring changes are also required.
Parameter:
13 Supply Voltage
Function:
Adjusts the PCS100 AVC-20 working voltage
Access:
Tech
Range:
0.00 V to 1599.95 V
Default:
Nameplate rating of PCS100 AVC-20
Setting Up:
Set to nominal supply voltage ± 10% (RMS)
Parameter:
14 Supply Frequency
Function:
Set the supply voltage frequency.
Access:
Tech
Range:
40 Hz to 400 Hz
Default:
Nameplate rating of PCS100 AVC-20
Setting Up:
Set to nominal supply frequency
Parameter:
15 Sag Threshold
Function:
Power quality meter sag recording threshold.
Access:
Operator
Range:
0 % to 399.99%
Unit
Percentage of parameter
13 Supply Voltage
Default:
90%