58
PCS100 AVC-20
User Manual
Note:
This parameter adjusts the recording threshold for sag events recorded in the
Event Log and on the Summary Page. It does not alter the operation of the PCS100
AVC-20.
Parameter:
16 Surge Threshold
Function:
Power quality meter surge recording threshold.
Access:
Operator
Range:
0 % to 399.99%
Unit
Percentage of parameter
13 Supply Voltage
Default:
110%
Note:
This parameter adjusts the recording threshold for surge events recorded in the
Event Log and on the Summary Page. It does not alter the operation of the PCS100
AVC-20.
Table 8
-
3: Menu 1 System Electrical Parameters
8.3.4
Menu 2 Commissioning
2 Commissioning
The menu contains parameters for commissioning and testing
Note: This menu is only visible with Tech login
Parameter:
20 Config Check Mode
Function:
Provides a check of the phasing of the supply cables.
Access:
Tech
Range:
True / False
Setting Up:
When this parameter is set to True the output regulation voltages will be V1-100%, V2-
105% and V3-110% of the parameter
13 Supply Voltage
setting.
Note:
This check should be performed during commissioning. See section 2UCD280000E004
PCS100 AVC-20 Commissioning Checklist.
Parameter:
21 Test Mode
Function:
Selects test modes.
Access:
Tech
Range:
15 test options
Default:
NONE
Parameter:
22 Test Voltage
Function:
Selects output voltage under Test Mode.
Access:
Tech
Range:
-4.0000 to 3.9999
Units
PU. Base =
13 Supply Voltage
Default:
0.0000
Parameter:
23 Test Frequency
Function:
Selects output frequency under Test Mode.
Access:
Tech
Range:
-200.00 to 199.994
Units
Hz
Default:
Nameplate rating of PCS100 AVC-20