The Modbus TCP server responds to reads from the cached addresses in typically less than 3 milliseconds.
However, the latency in a parameter changing value (the time it takes for the cached values to be refreshed) is
typically around 3 seconds.
10.3.3
Modbus TCP User Parameters
The following table lists the user parameters available from the PCS100 AVC-20.
The address listed is the offset (raw) address. For 4xxxx address add 40001 to the offset address. Each address
refers to a 16-bit register.
Address
Name
Access
Type
Raw Value & Scaling
1
Product
Status
Read Only
16-bit,
Enum
0
–
FAULT
1
–
BYPASS
2
–
STARTING
3
–
RUN
4
–
STOPPING
5
–
AUTO BYPASS
2
Warning
Indication
Read Only
16-bit,
Enum
0
–
NOT WARNING
1
–
WARNING
3
Inhibit
Indication
Read Only
16-bit,
Enum
0
–
NOT INHIBIT
1
–
INHIBIT
4
Rated Voltage Read Only
16-bit,
Signed
Voltage (line-to-line RMS volts) = raw value
e.g., raw value = 480
Voltage = 480V
5
Rated
Frequency
Read Only
16-bit,
Signed
Frequency (Hz) = raw value / 32
e.g., raw value = 1920
Frequency = 60Hz
6
Rated Current Read Only
16-bit,
Signed
Current (RMS Amps) = raw value
e.g., raw value = 500
Current = 500A
7
Input Voltage
V1-V2
Read Only
16-bit,
Signed
Voltage (line-to-line RMS volts)
= raw value x
13 Supply Voltage
/ 8192
e.g., raw value = 7782
rated voltage = 480V
Voltage = 456V
Voltage (% of rated voltage)
= raw value x 100 / 8192
e.g., raw value = 8192
Voltage = 100%
8
Input Voltage
V2-V3
Read Only
16-bit,
Signed
9
Input Voltage
V3-V1
Read Only
16-bit,
Signed
10
Output
Voltage V1-V2
Read Only
16-bit,
Signed
11
Output
Voltage V2-V3
Read Only
16-bit,
Signed
12
Output
Voltage V3-V1
Read Only
16-bit,
Signed
13
Load Current
I1
Read Only
16-bit,
Signed
Current (RMS Amps)
= raw value x
10 System Current
/ 8192
e.g., raw value = 5792
rated current = 500A
Current = 354A
Current (% of rated current)
= raw value x 100 / 8192
e.g., raw value = 4096
Current = 50%
14
Load Current
I2
Read Only
16-bit,
Signed
15
Load Current
I3
Read Only
16-bit,
Signed