Note
Action
If it is not connected, repair the
connection and go to step six.
Check that the FlexPendant cable is correctly
connected to the controller through the HMI signal
connector, X4.
2
Check the pins in the connector.
If it is ok, go to the next step.
•
If damage is found, replace
the FlexPendant cable and
go to step six.
•
If it is ok, go to the next
step.
Check the FlexPendant cable for any damage.
3
If possible, test by connecting another FlexPend-
ant. This is to eliminate the FlexPendant and cable
as error sources; Test the FlexPendant with a
different controller to eliminate the controller as
error source.
4
If it is not ok, contact your local
ABB.
Check that the FlexPendant works normally.
Tip
This is detailed in section
.
5
Product manual - OmniCore V400XT
359
3HAC081697-001 Revision: A
© Copyright 2022-2023 ABB. All rights reserved.
7 Troubleshooting
7.2.5 Problem starting or connecting the FlexPendant
Continued