Note
Action
Measure the resistance between bleeder con-
nector (X10.1 and X10.2)
•
If the connection is OK, proceed with
step
•
If there is a problem with the connection,
repair the connection and start over.
•
If the resistance of bleeder is greater
than 20 ohm or less than 10 ohm, replace
the bleeder. See
.
Check the bleeder connection at
X10.
CAUTION
Before measuring the bleeder res-
istance, do the following:
•
Shut down the power and
wait 1 minute.
•
Disconnect X10.
10
See
Replacing the power unit on page 242
The unit may be faulty. Replace the
power unit.
11
Product manual - OmniCore V400XT
393
3HAC081697-001 Revision: A
© Copyright 2022-2023 ABB. All rights reserved.
7 Troubleshooting
7.3.6 Troubleshooting the HVLP power unit (DSQC3072)