MANUAL MOTOR STARTER GUIDE
APRIL 19
24/80
2.4.6 Accessories and enclosures
Since manual motor starters combine the functions of multiple components, such as circuit-breakers, disconnect
switches, and overload relays, they are offered with many of the same types of accessories. Thus, the manual motor
starters can be extended with auxiliary contacts which can be connected either on the side or - especially to save
space - on the front. Also, undervoltage releases are available, and shunt releases complement the product range.
With the help of separately available adapters can the manual motor starter easily and quickly, build to a compact
starter combinations of motor protection switch and contactor.
Signaling and
status indica-
tion
Auxiliary contacts
HK1, HKF1
Signal contact alarms
SK1
Short-circuit signaling contact
CK1
Increasing
functionality
Undervoltage releases
UA1
Shunt trips
AA1
Current limiters
S803W
Reducing in-
stallation time
and saving
space
Three-phase busbar
PSx
Feeder (in-feed) terminal blocks
S1-Mx
Connecting Link
BEA
External oper-
ation and
enclosures
Handles and shafts, NEMA Types 1, 3R, 12
Shaft alignment accessories
Door-mount kits, NEMA Type 12
DMS132
Enclosures, NEMA Type 12
IB132
Auxiliary and signaling contacts can be combined to provide external status indication for a variety of conditions and
states. The table below shows an overview of the functionality of these contact types.
Contact type
Condition / state of manual motor starter
OFF
ON
Signaling
contact
Short-cir-
cuit trip
Undervolt-
age
release
Shunt trip
HK1,
HKF1
Auxiliary
contacts
Change posi-
tion with the
main contacts
Normally-
open
O
X
O
O
O
O
Normally-
closed
X
O
X
X
X
X
SK1
Signal con-
tact alarms
Signals trip-
ping by short-
circuit or over-
load
Normally-
open
O
O
X
X
X
X
Normally-
closed
X
X
O
O
O
O
CK1
Short-circuit
indicators
Signals trip-
ping by short-
circuit
Normally-
open
O
O
O
X
O
O
Normally-
closed
X
X
X
O
X
X
O = Open; X = Closed
Table 9: Condition / state of manual motor starter.