MANUAL MOTOR STARTER GUIDE
APRIL 19
22/80
2.4 Product offering
ABB provides a comprehensive manual motor starter. Worldwide the manual motor starters device types are divided
into three ranges to simplify selection, coordination, and installation:
-
MS116 with a standard performance range up to 32 A
-
MS132 / MO132 with high performance ranges up to 32 A
-
MS165 / MO165 with high performance ranges up to 80 A
-
MS132-T with high performance ranges for transformer protection
MS116
MS132
MS132-K
MS165
MS132-T
MS132-KT
Thermal protection
X
X
X
X
Electromagnetic protection
X
X
X
X
Phase loss sensitivity
X
X
X
X
Switch position
ON/OFF
ON/OFF/TRIP
ON/OFF/TRIP
ON/OFF/TRIP
Magnetic trip indication
X
X
X
Lockable handle without accessories
X
X
X
Disconnection function
X
X
X
X
Width
45 mm
45 mm
55 mm
45 mm
Rated operational current I
e
0.1 ... 32 A
0.1 ... 32 A
10 ... 80 A
0.1 ... 25 A
Short circuit breaking capacities
up to 100 kA
up to 100 kA
up to 100 kA
up to 100 kA
Ambient air temperature (w/o derating)
-25 ... +55 °C
-25 ... +60 °C
-25 ... +60 °C
-20 ... +60 °C
MO132
MO165
Thermal protection
Electromagnetic protection
X
X
Phase loss sensitivity
Switch position
ON/OFF/TRIP
ON/OFF/TRIP
Magnetic trip indication
Lockable handle without accessories
X
X
Disconnection function
X
X
Width
45 mm
55 mm
Rated operational current I
e
0.1 ... 32 A
10 ... 80 A
Short circuit breaking capacities
up to 100 kA
up to 100 kA
Ambient air temperature (w/o derating)
-25 … +60 °C
-25 ... +60 °C
Table 8: Product range of all manual motor starters.