LME620-AI / PME120-AI / EAN823 / EBN853 / EBN861
ELECTRONIC UNIT | OI/PME/LME/EAN823/EBN853/EBN861-EN REV. E
11
Delivery status
The individual actuator configuration may vary from the
standard setup above. This information can be displayed via the
user interface.
Unless otherwise specified by the user, the electronic units are
delivered with the following standard configuration:
Conventional communication
Parameter Setting
Function selection
Positioner, parameter: set point
Set point function
Analog set point
Set point range
4 to 20 mA
Set point characteristic
Linear; set point = position value
Actual value range
4 to 20 mA
Nominal torque / rated force in
±direction
100 %
Automatic speed in ±direction:
100 %
Action in 0 % / 100 % end
position
Keep leak-tight with nominal torque / rated
force
Digital inputs
Digital input 1 Manual / Automatic
switching,
Digital input 2 / 3 Travel command ±
Digital outputs
Digital output 1 ready for operation / error
message,
Digital output 2 / 3 end position signaling
0 % / 100 %
Brake Away Function
Deactivated
Shut-off function
Deactivated
Positioning loop monitoring
Deactivated
Set point monitoring
Deactivated
Alarm Type
Deactivated
Action after restoration of
power
Switch to Automatic
Working range of actuator
Not set
PROFIBUS DP® communication
Parameter Setting
Function selection
Positioner, parameter: set point
Set point function
Digital
Set point range
4 to 20 mA
Set point characteristic
Linear; set point = position value
Actual value range
Digital
Nominal torque / rated force in
±direction
100 %
Automatic speed in ±direction:
100 %
Action in 0 % / 100 % end
position
Keep leak-tight with nominal torque / rated
force
Digital outputs
Digital output 1 / 2 end position signal 0
% / 100 %
Brake Away Function
Deactivated
Shut-off function
Deactivated
Positioning loop monitoring
Deactivated
Communication monitoring
PROFIBUS DP® / V0:
Activated
Lock in last position
PROFIBUS DP® / V1:
Activated
After delay time has elapsed (standard
configuration 5 s)
Lock in last position
Alarm Type
Deactivated
Action after restoration of
power
Switch to Automatic
Working range of actuator
Not set