LME620-AI / PME120-AI / EAN823 / EBN853 / EBN861
ELECTRONIC UNIT | OI/PME/LME/EAN823/EBN853/EBN861-EN REV. E
25
Electrical data for inputs and outputs
Power supply
PME120-AI / LME620-AI
Supply voltage
115 V AC (94 to 130 V) or 230 V AC (190 to 260 V); 47.5 to 63 Hz; single-phase
Current consumption at the electronic unit [A]
(AC 115 V / AC 230 V)
LME620-AI, PME120 l
max
at 115 V: 1.0 A
l
max
at 230 V: 0.5 A
l
pos
(115 V + 230 V):
approx. 40 to 50 % of l
max
Actuators for low temperature design LME620-AI,
PME120
l
max
at 115 V: 1.4 A
l
max
at 230 V: 0.7 A
External fuse
16 A; time-lag
EBN853
Supply voltage (standard actuators)
115 V AC (94 to 130 V) or 230 V AC (190 to 260 V); 47.5 to 63 Hz; single-phase
Supply voltage (Ex actuators)
115 V AC (94 to 127 V) or 230 V AC (190 to 253 V); 47.5 to 63 Hz; single-phase
Current consumption at the electronic unit
(AC 115 V / AC 230 V)
Actuator l
max
at 115 V
l
max
at 230 V
l
pos
(115 V + 230 V):
approx. 40 to 50 % of l
max
RHD(E)250-10 1.8
A
0.9
A
RHD(E)500-10
2.2 A
1.1 A
RHD(E)800-10
5.0 A
2.5 A
RHD(E)1250-12
5.0 A
2.5 A
RHD(E)2500-25
5.0 A
2.5 A
RHD(E)4000-40 5.8
A
2.7
A
RHD(E)8000-80
5.0 A
2.5 A
RSD(E)10-5,0
2.2 A
1.1 A
RSD(E)10-10,0 3.6
A
1.8
A
RSD(E)20-5,0 3.6
A
1.8
A
RSD(E)20-7,5
4.8 A
2.4 A
RSD(E)50-3,0
5.0 A
2.5 A
RSD100-1.5
5.0 A
2.5 A
RSD200-0.7
5.0 A
2.5 A
External fuse for electronic unit