18
LME620-AI / PME120-AI / EAN823 / EBN853 / EBN861
ELECTRONIC UNIT | OI/PME/LME/EAN823/EBN853/EBN861-EN REV. E
hange from two to one column
… 6 Electrical connections
… Conductor cross-section on universal plug
PME / LME
Crimp pins
Screw terminals (optional)
Separate
electronic unit
Cable cross-section Motor / brake / heater:
Signals:
max. 1.5 mm
2
(16 AWG)
max. 0.5 mm
2
(20 AWG)
Motor / brake / heater /
signals:
0.2 to 2.5 mm
2
(24 to 14 AWG)
Contact surface
Motor / brake / signals:
Heater:
Gold-plated
Silver-plated
Motor / brake / signals:
Heater:
Gold-plated
Silver-plated
integrated
electronic unit
Cable cross-section Power supply:
Signals:
max. 2.5 mm
2
(14 AWG)
max. 0.5 mm
2
(20 AWG)
Power supply / signals:
0.2 to 2.5 mm
2
(24 to 14 AWG)
Contact surface
Power supply /signals:
Gold-plated
Power supply /signals:
Gold-plated
Change from one to two columns
Conductor cross-section on electronic unit
EAN823 – screw terminals
Motor/brake
rigid: 0.2 to 6 mm
2
(24 to 10 AWG)
flexible: 0.2 to 4 mm
2
(24 to 12 AWG)
Mains
rigid: 0.5 to 6 mm
2
(20 to 10 AWG)
flexible: 0.5 to 4 mm
2
(20 to 12 AWG)
Signals
rigid: 0.5 to 6 mm
2
(20 to 10 AWG)
flexible: 0.5 to 4 mm
2
(20 to 12 AWG)
EBN853 – Screw terminals
Motor/brake
rigid: 0.2 to 6 mm
2
(24 to 10 AWG)
flexible: 0.2 to 4 mm
2
(24 to 12 AWG)
Mains
rigid: 0.5 to 6 mm
2
(20 to 10 AWG)
flexible: 0.5 to 4 mm
2
(20 to 12 AWG)
Signals
rigid: 0.5 to 4 mm
2
(20 to 12 AWG)
flexible: 0.5 to 2.5 mm
2
(20 to 14 AWG)
EBN861 – Screw terminals
Motor / brake
rigid: 0.2 to 6 mm
2
(24 to 10 AWG)
flexible: 0.2 to 4 mm
2
(24 to 12 AWG)
Mains
rigid: 0.5 to 6 mm
2
(20 to 10 AWG)
flexible: 0.5 to 4 mm
2
(20 to 12 AWG)
Signals
rigid: 0.5 to 4 mm
2
(20 to 12 AWG)
flexible: 0.5 to 2.5 mm
2
(20 to 14 AWG)
Cable glands
The actuators and electronic units are supplied without cable
glands. Suited cable glands must be installed on site.
Tap holes for cable glands
metric
optional adapters for*
Signal cable
M20 × 1.5 (2 ×)
PG 16 (2 ×)
NPT ½ in (2 ×)
Motor cable
M25 × 1.5 (1 ×)
PG 21 (1 ×)
NPT ¾ in (1 ×)
* Adapter for PG or NPT thread must be ordered separately
Selection of suited connection cables
Please observe the following information when selecting cables:
• Use shielded cables for the motor/brake cable, the
sensor cable, and the signal cable to the control
system/controller.
• Connect the shielding of the motor/brake cable and the
sensor cable on both sides (to the actuator and to the
Contrac electronic unit).
Change from two to one column