26
LME620-AI / PME120-AI / EAN823 / EBN853 / EBN861
ELECTRONIC UNIT | OI/PME/LME/EAN823/EBN853/EBN861-EN REV. E
… 6 Electrical connections
… Electrical data for inputs and outputs
EBN861
Supply voltage (standard actuators)
230 V AC (190 to 260 V); 47.5 63 Hz; single-phase
Supply voltage (Ex actuators)
230 V AC (190 to 253 V); 47.5 63 Hz; single-phase
Current consumption at the electronic unit
(AC 230 V)
Actuator l
max
at 230 V
l
pos
(230 V): approx. 40 to 50 % of l
max
RHD(E)2500-10 5.3
A
RHD(E)4000-10 10.0
A
RHD8000-12 8.0
A
RHDE8000-15 8.0
A
RHD(E)16000-30 12.5
A
RSD(E)50-10 6.4
A
RSD100-10.0 12.5
A
RSD200-5.0 13.0
A
External fuse for electronic unit
Safety fuse 35 A (Lindner) + thermal circuit breaker 16 A (ETA); fuses are in the scope of delivery
Binary inputs and outputs - communication
Conventional communication
Analog input
0 / 4 to 20 mA, internal load: 300
Ω
Analog output
0 / 4 to 20 mA, electrically isolated, maximum load: 500
Ω
3 digital inputs, 1 to 3
Digital 0:
−
3 to 5 V or open, electrically isolated
Digital 1: 12 to 35 V, electrically isolated
3 digital outputs, 1 to 3
Potential-free relay contact, max. 60 V, 150 mA
Digital communication
RS232 for commissioning and service, optionally FSK / HART®
Default settings
Conventional communication
on page 11
Voltage output U
V
24 V, 15 mA, electrically isolated, for scanning external contacts, or similar applications
Connection for transmitter (optional)
Supply for two-wire transmitter with activated process controller in Contrac
Individual settings