Additional parameters for "Control
function = Heating"
Settings
Comments
Control parameter
•
via system type
•
Free paramaterization
–
Type of heating system
For "PI continuous"
and "PI PWM (1-bit)"
•
Hot-water heating
•
Electric heating
(1.5 K/50 min)
•
Floor heating (4
K/200 min)
Type of heating system
For "FanCoil"
FanCoil (4 K/90 min)
P amount heating (1/10 K)
10 … 100
Only available when parameter "Control
parameter" is set on "Free
paramaterization".
I-component heating (min.)
0 … 255
max. control value heating
0 … 255
–
min. control value heating
0 … 255
–
Additional parameters for "Control
function = Cooling"
Settings
Comments
Control parameter
•
via system type
•
Free paramaterization
–
P amount cooling (1/10 K)
10 … 100
Only available when parameter "Control
parameter" is set on "Free
paramaterization".
I-component cooling (min.)
0 … 255
max. control value cooling
0 … 255
–
min. control value cooling
0 … 255
–
Note
The following parameters are available only when parameter "Control type heating" or "Control
type cooling" is set on "PI continuous", or "FanCoil".
Additional parameters for "Control
function = Heating"
Settings
Comments
Control value difference PI continuous for
sending of the control value heating
•
deactivated
•
2 %
•
5 %
•
10 %
–
Additional parameters for "Control
function = Cooling"
Settings
Comments
Control value difference PI continuous for
sending of the control value cooling
•
deactivated
•
2 %
•
5 %
•
10 %
–