KNX Technical Reference Manual 

   

ABB-i-Bus

®

-KNX Millenium 

 

Description of applications / 

objects

 

 

 

 

 

 

 

 

 

 

 

 

 

KNX Technical Reference Manual | 1473-1-7819 

— 61 — 

   

 

11.4 

Application "Operating mode settings"  

 

With application "Operating mode settings" manual operation can be influenced. Also various indications and 
forms of display of the device can be specified with it. 
 

Parameters 

 

General parameter 

Settings 

Comments 

Primary function

 

  Setpoint temperature adjustment 

  Fan stage adjustment 

– 

Jump-back time into primary function

 

  5 s 

  10 s 

  20 s 

  30 s 

  1 min 

  2 min 

  4 min 

– 

Temperature adjustment in ECO mode

 

  deactivated 

  activated 

– 

Display of actual temperature

 

  deactivated 

  activated 

– 

 
 

Parameters for "Temperature unit" 

Settings 

Comments 

Temperature unit

 

  °C 

  °F 

– 

Setting temperature unit via object

 

  deactivated 

  activated 

– 

 
 

Parameters for "Brightness setting" 

Settings 

Comments 

Day/Night mode

 

  deactivated 

  activated 

– 

Brightness of display backlighting

 

  dark 

  bright 

– 

 
 

Parameters for "Extended settings" 

Settings 

Comments 

Colour range of display backlighting

 

  Coloured 

  black-white 

– 

Backlighting of icons

 

  deactivated 

  activated 

– 

Font

 

  Normal 

  Filigree 

– 

 
 

Objects 

 

No. 

Object name 

Data type 

Flags 

 

 

– 

– 

 
 
 

 

Содержание -i-Bus-KNX Millenium

Страница 1: ...1473 1 7819 Rev 01 12 2012 KNX Technical Reference Manual ABB i Bus KNX Millenium Room temperature controller incl BAU 6124 20 981 500 AMD70053 AN...

Страница 2: ...lectrical connection 16 7 Commissioning 17 7 1 Software 17 7 1 1 Preparatory steps 17 7 1 2 Assigning a physical address 17 7 1 3 Assigning the group address es 18 7 1 4 Selecting the application prog...

Страница 3: ...l 1473 1 7819 3 11 3 2 Parameters for Control function Heating 30 11 3 3 Parameters for Control function Cooling 36 11 3 4 Parameters for Control function Heating and cooling 42 11 3 5 Parameters for...

Страница 4: ...and adhered to Modifications and repairs to the product must only be undertaken if the manual expressly permits this It is only the adherence to the safety instructions and all safety and warning sym...

Страница 5: ...signal word Caution indicates a possibly dangerous situation which could lead to slight or moderately serious injury Attention damage to property This symbol indicates a possibly harmful situation Non...

Страница 6: ...ilator convector with a fan coil actuator or a conventional heating and cooling system Extensive functions are available for the room temperature controller The scope of the application is contained i...

Страница 7: ...odification excludes the liability of the manufacturer for the damages caused It voids the warranty of the manufacturer 2 5 Environment Consider the protection of the environment Used electric and ele...

Страница 8: ...This makes it possible to very quickly adjust the temperature in a hotel room to the individual wishes of the guests The device supports the full function for international hotel applications It can f...

Страница 9: ...nical Reference Manual 1473 1 7819 9 3 2 Overview of devices 3 2 1 Front Position Function 1 Push buttons 2 Rotary control element 3 Display 3 2 2 Rear Position Function 1 KNX connection Note Observe...

Страница 10: ...on KNX Technical Reference Manual 1473 1 7819 10 3 3 Cover frame and support ring Note A cover frame and a support ring from the Millenium program are additionally required see the following illustrat...

Страница 11: ...ne 24 V DC Bus subscribers 1 12 mA KNX connection Bus connecting terminal screwless Protection type IP20 according to DIN EN 60529 Ambient temperature range 5 45 C Storage temperature range 20 70 C Di...

Страница 12: ...rrect installation endangers your life and that of the user of the electrical system Incorrect installation can cause serious damage to property e g due to fire The minimum necessary expert knowledge...

Страница 13: ...eight of approximately 150 cm from the floor and 50 cm from a door frame The room temperature controller should be installed on a wall opposite a radiator The angles of room architecture should not se...

Страница 14: ...lectrical connection KNX Technical Reference Manual 1473 1 7819 14 Wetting the room temperature controller with fluids is to be avoided Just as heat radiated from electric loads can impair the tempera...

Страница 15: ...g on page 10 1 The side of the support ring with the marking TOP must be aligned toward the top Now insert the device into the support ring in such a way that both sides with the marking TOP on the de...

Страница 16: ...Manual 1473 1 7819 16 3 Then plug the cover frame onto the support ring Separate order see also chapter Cover frame and support ring on page 10 Fig 6 Attaching the cover frame 6 4 Electrical connecti...

Страница 17: ...Software ETS from version ETS 3 0 f Use the appropriate commissioning tool Power Tool for the parameter settings 7 1 1 Preparatory steps 1 Connect a PC via the KNX interface e g the commissioning int...

Страница 18: ...the application program Please contact our Internet support unit www Busch Jaeger com The application is loaded into the device via the ETS 7 1 5 Differentiating the application program Various funct...

Страница 19: ...on for activating deactivating the room temperature controller Note The basic setting of the display always indicates the set point temperature or the fan speed level Starting from paragraph General c...

Страница 20: ...ntilation Ventilation deactivated or on standby Fan speed level during manual ventilation Room temperature controller On or Off Eco mode 8 3 LED colour concept 8 3 1 Explanation Colour Meaning White S...

Страница 21: ...functions of the buttons in connection with the rotary control element and the display are described in the following The precise function is fixed via the assigned application function and their par...

Страница 22: ...perature is shown in the display Whenever the set point temperature is unequal to the actual temperature the indication changes from white to orange or blue Here the background is appropriately colour...

Страница 23: ...esired fan speed level or the desired operating status is displayed 3 Press the button Fan speed levels or wait until the set time expires The adjustment is stored Fig 13 Device in fan speed level set...

Страница 24: ...the ECO mode absence state 2 After a renewed press of the ECO mode button the device returns to the settings that were active prior to the activation of ECO mode Fig 14 Device in ECO mode Note During...

Страница 25: ...th slightly moistened with a soap solution can be used Caustic cleaning agents or solvents must not be used 10 Maintenance The unit is maintenance free In case of damage e g during transport or storag...

Страница 26: ...mperature controller contains the applications listed in the following KNX application Page Temperature reading 27 RTC settings 29 Operating mode settings 61 Depending on which device and application...

Страница 27: ...s not even Parameters General parameter Settings Comments Internal temperature measurement activated deactivated Cycle time for sending of the actual temperature mm ss 00 25 90 00 Additional parameter...

Страница 28: ...e Manual ABB i Bus KNX Millenium Description of applications objects KNX Technical Reference Manual 1473 1 7819 28 Objects No Object name Data type Flags 0 Output 2 Byte EIS5 DPT 9 001 C T 1 Alarm 1 B...

Страница 29: ...l parameter Settings Comments Operating as RTC extension unit activated deactivated Parameters for Temperature reading Settings Comments Operating mode for fault Heating Cooling Only available when pa...

Страница 30: ...ttings Comments Additional heating stage deactivated activated Parameters for Setting operating modes Settings Comments Operating mode after reset Standby Comfort ECO mode Frost heat protection Genera...

Страница 31: ...ea for manual set value setting is set on 1 K 15 K Resetting of the manual adjustment for receipt of a basic set value deactivated activated Resetting of the manuel adjustment for change of operation...

Страница 32: ...heating Normal inverse Hysteresis heating 1 10 K 3 255 Only available when parameter Control type heating is set on 2 point 1 bit Off On or 2 point 1 byte 0 100 cyclical sending of the control value...

Страница 33: ...et on PI continuous or on FanCoil Additional parameters for Control function Heating Settings Comments Control value difference PI continuous for sending of the control value heating deactivated 2 5 1...

Страница 34: ...ted Position output only manuel manual and auto Format of the stage output 0 5 0 255 1 bit m of n 1 bit 1 of n Control value output for fan stage 1 heating 0 255 0 255 Control value output for fan sta...

Страница 35: ...set on activated Additional parameters for Control function Heating Settings Comments Output additional stage heating 2 point 1 bit Off On 2 point 1 byte 0 100 Mode of the control value of the additi...

Страница 36: ...ents Operating mode after reset Standby Comfort ECO mode Frost heat protection Parameters for Alarm function Settings Comments Condensate water alarm deactivated activated Dew point alarm deactivated...

Страница 37: ...r manual set value setting is set on 1 K 15 K Resetting of the manual adjustment for receipt of a basic set value deactivated activated Resetting of the manuel adjustment for change of operation mode...

Страница 38: ...Mode of the control value for cooling Normal inverse Hysteresis cooling 1 10 K 3 255 Only available when parameter Control type cooling is set on 2 point 1 bit Off On or 2 point 1 byte 0 100 cyclical...

Страница 39: ...et on PI continuous or on FanCoil Additional parameters for Control function Cooling Settings Comments Control value difference PI continuous for sending of the control value cooling deactivated 2 5 1...

Страница 40: ...eps 5 steps Evaluation stage status deactivated activated Control value output for fan stage 1 cooling 0 255 0 255 Control value output for fan stage 2 cooling 0 255 0 255 Control value output for fan...

Страница 41: ...set on activated Additional parameters for Control function Cooling Settings Comments Output additional stage cooling 2 point 1 bit Off On 2 point 1 byte 0 100 Mode of the control value of the additi...

Страница 42: ...ects Output control value additional stage heating and cooling via 1 object via 2 objects Additional heating stage deactivated activated Additional cooling stage deactivated activated Parameters for S...

Страница 43: ...r Set values manual Settings Comments Area for manual set value setting deactivated 1 K 2 K 3 K 4 K 5 K 6 K 7 K 8 K 9 K 10 K 11 K 12 K 13 K 14 K 15 K max manual lowering during cooling mode 0 15 K 0 1...

Страница 44: ...ndby heating setting dependent K 0 15 Setpoint temperature ECO heating setting dependent K 0 15 Setpoint frost C 5 40 Parameters for Dead zone Settings Comments Distance heating cooling comfort K 1 10...

Страница 45: ...Mode of the control value for heating Normal inverse Hysteresis heating 1 10 K 3 255 Only available when parameter Control type heating is set on 2 point 1 bit Off On or 2 point 1 byte 0 100 cyclical...

Страница 46: ...l value heating 0 255 Additional parameters for Control function Cooling Settings Comments Control parameter via system type Free paramaterization P amount cooling 1 10 K 10 100 Only available when pa...

Страница 47: ...te The following parameters are available only when parameter Control type heating or Control type cooling is set on PI continuous or PI PWM 1 bit Additional parameters for Control function Heating Se...

Страница 48: ...stages 3 steps 5 steps Evaluation stage status deactivated activated Control value output for fan stage 1 heating 0 255 0 255 Control value output for fan stage 2 heating 0 255 0 255 Control value ou...

Страница 49: ...vated Control value output for fan stage 1 cooling 0 255 0 255 Control value output for fan stage 2 cooling 0 255 0 255 Control value output for fan stage 3 cooling 0 255 0 255 Control value output fo...

Страница 50: ...e additional stage heating Normal inverse Temperature difference additional stage heating x 0 1K 0 255 upper hysteresis of the additional stage heating x 0 1K 0 255 cyclical sending of the control val...

Страница 51: ...ects Output control value additional stage heating and cooling via 1 object via 2 objects Additional heating stage deactivated activated Additional cooling stage deactivated activated Parameters for S...

Страница 52: ...r Set values manual Settings Comments Area for manual set value setting deactivated 1 K 2 K 3 K 4 K 5 K 6 K 7 K 8 K 9 K 10 K 11 K 12 K 13 K 14 K 15 K max manual lowering during cooling mode 0 15 K 0 1...

Страница 53: ...K 0 15 Setpoint temperature ECO heating setting dependent K 0 15 Setpoint frost C 5 40 Parameters for Dead zone Settings Comments Distance heating cooling comfort K 1 10 min dead zone heating cooling...

Страница 54: ...Mode of the control value for heating Normal inverse Hysteresis heating 1 10 K 3 255 Only available when parameter Control type heating is set on 2 point 1 bit Off On or 2 point 1 byte 0 100 cyclical...

Страница 55: ...ntrol parameter via system type Free paramaterization P amount cooling 1 10 K 10 100 Only available when parameter Control parameter is set on Free paramaterization I component cooling min 0 255 max c...

Страница 56: ...te The following parameters are available only when parameter Control type heating or Control type cooling is set on PI continuous or PI PWM 1 bit Additional parameters for Control function Heating Se...

Страница 57: ...vated activated Position output only manuel manual and auto Format of the stage output 0 5 0 255 1 bit m of n 1 bit 1 of n Control value output for fan stage 1 heating 0 255 0 255 Control value output...

Страница 58: ...vated Control value output for fan stage 1 cooling 0 255 0 255 Control value output for fan stage 2 cooling 0 255 0 255 Control value output for fan stage 3 cooling 0 255 0 255 Control value output fo...

Страница 59: ...e additional stage heating Normal inverse Temperature difference additional stage heating x 0 1K 0 255 upper hysteresis of the additional stage heating x 0 1K 0 255 cyclical sending of the control val...

Страница 60: ...U 19 Reset onsite operation 1 Bit EIS1 DPT 1 001 C W U 20 Heating and cooling control value 1 Byte EIS6 DPT 5 001 C W T U 21 Cooling control value 1 Byte EIS6 DPT 5 001 C W T U 22 Cooling control val...

Страница 61: ...mp back time into primary function 5 s 10 s 20 s 30 s 1 min 2 min 4 min Temperature adjustment in ECO mode deactivated activated Display of actual temperature deactivated activated Parameters for Temp...

Страница 62: ...ake technical changes as well as changes to the contents of this document without prior notice The detailed specifications agreed to at the time of ordering apply to all orders ABB accepts no responsi...

Отзывы: