Note
The following parameters are available only when parameter "Additional heating stage" or
"Additional cooling stage" is set on "activated".
Additional parameters for "Control
function = Heating"
Settings
Comments
Output additional stage heating
•
2-point 1-bit (Off/On)
•
2-point 1-byte (0/100%)
–
Mode of the control value of the additional
stage heating
•
Normal
•
inverse
–
Temperature difference additional stage
heating (x 0,1K)
0 … 255
–
upper hysteresis of the additional stage
heating (x 0,1K)
0 … 255
–
cyclical sending of the control value
additional stage heating (min)
1 … 60
–
Additional parameters for "Control
function = Cooling"
Settings
Comments
Output additional stage cooling
•
2-point 1-bit (Off/On)
•
2-point 1-byte (0/100%)
–
Mode of the control value of the additional
stage cooling
•
Normal
•
inverse
–
Temperature difference additional stage
cooling (x 0,1K)
0 … 255
–
lower hysteresis of the additional stage
cooling (x 0,1K)
0 … 255
–
cyclical sending of the control value
additional stage cooling (min)
1 … 60
–