Parameters for "Set values manual"
Settings
Comments
Area for manual set value setting
deactivated
+/-1 K
+/-2 K
+/-3 K
+/-4 K
+/-5 K
+/-6 K
+/-7 K
+/-8 K
+/-9 K
+/-10 K
+/-11 K
+/-12 K
+/-13 K
+/-14 K
+/-15 K
–
max. manual lowering during heating mode
(0 - 15 K)
0 … 15 K
Only available when parameter "Area for
manual set value setting" is set on "+/-
1 K … +/-15 K".
Resetting of the manual adjustment for
receipt of a basic set value
•
deactivated
•
activated
Resetting of the manuel adjustment for
change of operation mode
•
deactivated
•
only ECO mode adjustment for change
from ECO mode
•
activated
Reset onsite operation via options object
•
deactivated
•
with every value
•
with value 0
•
with value 1
–
Parameters for "Set values heating"
Settings
Comments
Base setpoint heating (°C)
10 … 40
–
Setpoint standby heating, setting
dependent (K)
0 … 15
–
Setpoint temperature ECO heating, setting
dependent (K)
0 … 15
–
Setpoint frost (°C)
5 … 40
–