Note
The following parameters are available only when parameter "Control type cooling" is set on "PI
continuous", "PI PWM (1-bit)" or on "FanCoil".
General parameters for "Control
function = Cooling"
Settings
Comments
Status object cooling
•
deactivated
•
activated
–
Control type cooling
•
2-point 1-bit (Off/On)
•
2-point 1-byte (0/100%)
•
PI continuous
•
PI PWM (1-bit)
•
FanCoil
–
Mode of the control value for cooling
•
Normal
•
inverse
–
Hysteresis cooling (1/10 K)
3 … 255
Only available when parameter "„Control
type cooling" is set on "2-point 1-bit
(Off/On)" or "2-point 1-byte (0/100%)".
cyclical sending of the control value cooling
(min)
1 … 60
–
Additional parameters for "Control
function = Cooling"
Settings
Comments
Control parameter
•
via system type
•
Free paramaterization
–
Type of cooling system
Für „PI continuous“
und „PI PWM (1-bit)“
Cooling ceiling (
–
Für „FanCoil“
FanCoil (4 K/90 min)
P amount cooling (1/10 K)
10 … 100
Only available when parameter "Control
parameter" is set on "Free
paramaterization".
I-component cooling (min.)
0 … 255
max. control value cooling
0 … 255
–
min. control value cooling
0 … 255
–