![ABB i-bus KNX ABA/S 1.2.1 Скачать руководство пользователя страница 93](http://html.mh-extra.com/html/abb/i-bus-knx-aba-s-1-2-1/i-bus-knx-aba-s-1-2-1_product-manual_3072093.webp)
ABB i-bus
®
KNX
Parameters
ABA/S 1.2.1 | 2CDC509086D0201 93
Function
Schematic diagram of controller:
Fig. 20: Schematic diagram of controller
Algorithms:
•
ControlValue = Proportiona Integra DerivativeValue
•
ProportionalValue = Deviation x ProportionalCoefficient
•
IntegralValue = IntegralVa Deviation x CycleTime / IntegralTime
•
DervativeValue = (Deviation - DeviationOld) / CycleTime x DerivativeTime
The controller calculates a new output value during the calculation cycle time of the logic engine (see
) (usually every 200 ms). The output sends on value change.
If the ControlValue exceeds the
Upper limit
or
Lower limit
(see parameters), the values are limited
accordingly and the IntegralValue is reduced.
If the Reset input = 1: the IntegralValue is set to 0.
Exception handling
For unlinked parameter inputs (Proportional Coefficient, Integral Time, Derivative Time) the function
element uses a 0.
Bus voltage failure, download and restart
The integral value is saved. The value is restored on restart.
Содержание i-bus KNX ABA/S 1.2.1
Страница 1: ... PRODUCT MANUAL ABB i bus KNX ABA S 1 2 1 Logic Controller ...
Страница 2: ......
Страница 6: ......
Страница 20: ......
Страница 105: ...ABB i bus KNX Operation ABA S 1 2 1 2CDC509086D0201 105 9 Operation 9 1 Manual operation Not relevant for this device ...
Страница 106: ......
Страница 108: ......
Страница 112: ......
Страница 114: ...ABB i bus KNX Appendix 114 2CDC509086D0201 ABA S 1 2 1 13 2 Notes ...
Страница 115: ...ABB i bus KNX Appendix ABA S 1 2 1 2CDC509086D0201 115 Notes ...