ABB i-bus
®
KNX
Parameters
ABA/S 1.2.1 | 2CDC509086D0201 85
7.10.30
Numeric Converter (N-CONV)
Description
The converter allows you to link different datapoint types and convert them.
Basics on datapoint types
The KNX specification distinguishes between main datapoint types and sub types, e.g.:
Main DPT type
DPT sub type
DPT name
1.xxx
1,001
DPT_SWITCH
1,008
DPT_UPDOWN
1,100
DPT_HEAT/COOL
Main type: Defines a data width.
Subtype: Defines a data width and unit.
Application
•
Conversion between different units of measurement, e.g. °C and °F or m/s and km/h
•
Conversion between different data types and widths
•
Conversion between a 2-byte float and a 4-byte float (e.g. temperature values)
Function
The following data types can be converted:
Data type
KNX Data Type
1 byte unsigned
5.xxx
1 byte signed
6.xxx
2 byte unsigned
7.xxx
2 byte signed
8.xxx
2 byte float
9.xxx
4 byte unsigned
12.xxx
4 byte signed
13.xxx
4 byte float
14.xxx
Содержание i-bus KNX ABA/S 1.2.1
Страница 1: ... PRODUCT MANUAL ABB i bus KNX ABA S 1 2 1 Logic Controller ...
Страница 2: ......
Страница 6: ......
Страница 20: ......
Страница 105: ...ABB i bus KNX Operation ABA S 1 2 1 2CDC509086D0201 105 9 Operation 9 1 Manual operation Not relevant for this device ...
Страница 106: ......
Страница 108: ......
Страница 112: ......
Страница 114: ...ABB i bus KNX Appendix 114 2CDC509086D0201 ABA S 1 2 1 13 2 Notes ...
Страница 115: ...ABB i bus KNX Appendix ABA S 1 2 1 2CDC509086D0201 115 Notes ...