ABB i-bus
®
KNX
Parameters
ABA/S 1.2.1 | 2CDC509086D0201 69
7.10.25
Modulo (MOD)
Description
Calculates the remainder from dividing one input value (Dividend) by another (Divisor).
Inputs
No.
DPT
Abbr.
Name
Visible
Description
1
8 bit or higher
Dev
Dividend
Always
2
Same as Input 1
Dor
Divisor
Always
Outputs
No.
DPT
Abbr.
Name
Visible
Description
1
Same as Input 1
R
Remainder
Always
Remainder of the division
2
1 bit
E
Error
Always
Indicates a division by 0
Parameters
None
Function
Whenever a telegram is received the output starts a recalculation independently if the value has changed.
Remainder and Error:
•
Dividend divided by Divisor and calculated value is within the valid range of the DPT. Calculation of
remainder:
o
R = value
o
E = 0 (false)
•
The input is not linked or the value of the Divisor = 0:
o
R = 0
o
E = 1 (true)
Other
Unlinked inputs are treated as if they did not exist.
Содержание i-bus KNX ABA/S 1.2.1
Страница 1: ... PRODUCT MANUAL ABB i bus KNX ABA S 1 2 1 Logic Controller ...
Страница 2: ......
Страница 6: ......
Страница 20: ......
Страница 105: ...ABB i bus KNX Operation ABA S 1 2 1 2CDC509086D0201 105 9 Operation 9 1 Manual operation Not relevant for this device ...
Страница 106: ......
Страница 108: ......
Страница 112: ......
Страница 114: ...ABB i bus KNX Appendix 114 2CDC509086D0201 ABA S 1 2 1 13 2 Notes ...
Страница 115: ...ABB i bus KNX Appendix ABA S 1 2 1 2CDC509086D0201 115 Notes ...