ABB i-bus
®
KNX
Parameters
72 2CDC509086D0201 | ABA/S 1.2.1
7.10.27
Staircase Light (STAIRC LIGHT)
Description
A timer which automatically resets the output to 0 (false) after a specified time has elapsed.
Inputs
No.
DPT
Abbr.
Name
Visible
Description
1
1 bit
Tr
Trigger
Always
2
4 byte unsigned
T
On-time
Parametrizable
Value in seconds;
according to KNX DPT
13.100
3
1 bit
R
Retrigger
Parametrizable
1 = yes
0 = no
Outputs
No.
DPT
Abbr.
Name
Invertible
Visible
Description
1
1 bit
O
Output
Yes
Always
1 (true), as long as the timer is
running
Input parameters
Name
Value
Visible
Description
On-time
Checkbox
Always
Activates input
T
(On-time)
Unsigned integer in [s]
If the checkbox is
deselected
Retrigger
Checkbox
Always
Activates input
R
(Retrigger)
Checkbox 2
If checkbox 1 is
deselected
When the
Retrigger
input
receives a value, the timer
resets to 0.
If the
On-time
checkbox is selected, the time value fields are not visible. The same applies to the
Retrigger
checkbox.
Содержание i-bus KNX ABA/S 1.2.1
Страница 1: ... PRODUCT MANUAL ABB i bus KNX ABA S 1 2 1 Logic Controller ...
Страница 2: ......
Страница 6: ......
Страница 20: ......
Страница 105: ...ABB i bus KNX Operation ABA S 1 2 1 2CDC509086D0201 105 9 Operation 9 1 Manual operation Not relevant for this device ...
Страница 106: ......
Страница 108: ......
Страница 112: ......
Страница 114: ...ABB i bus KNX Appendix 114 2CDC509086D0201 ABA S 1 2 1 13 2 Notes ...
Страница 115: ...ABB i bus KNX Appendix ABA S 1 2 1 2CDC509086D0201 115 Notes ...