ABB i-bus
®
KNX
Parameters
42 2CDC509086D0201 | ABA/S 1.2.1
Description of parameters
Change in %:
The value change is defined as follows:
(NEW_VALUE – LAST_SENT_VALUE) / LAST_SENT_VALUE
If NEW_VALUE = LAST_SENT_VALUE = 0, result is 0%
If NEW_VALUE <> 0 and LAST_SENT_VALUE = 0, result is 100%
Function
Whenever a telegram is received the output starts a recalculation independently if the value has changed.
Bus voltage failure, download and restart
The output values are not saved. Cyclic sending starts once the output receives a valid value.
Output values that cannot be sent on the bus (e.g. due to bus load or bus voltage failure) are overwritten
by newer values.
Element display
•
Element name
•
First group address
•
Data widths (1 bit, 2 bits, 4 bits, 1 byte, 2 bytes, 4 bytes, date, time, date/time, color)
Note
The first group address is the one that sends a value. The group addresses are displayed in the same
layout as in ETS (e.g. 2-level or 3-level).
Datapoint Type
Select the datapoint type required for displaying the value on the KNX accordingly.
All assigned group addresses are listed in Data Types in the
Properties
window. They cannot be changed
(read-only).
Содержание i-bus KNX ABA/S 1.2.1
Страница 1: ... PRODUCT MANUAL ABB i bus KNX ABA S 1 2 1 Logic Controller ...
Страница 2: ......
Страница 6: ......
Страница 20: ......
Страница 105: ...ABB i bus KNX Operation ABA S 1 2 1 2CDC509086D0201 105 9 Operation 9 1 Manual operation Not relevant for this device ...
Страница 106: ......
Страница 108: ......
Страница 112: ......
Страница 114: ...ABB i bus KNX Appendix 114 2CDC509086D0201 ABA S 1 2 1 13 2 Notes ...
Страница 115: ...ABB i bus KNX Appendix ABA S 1 2 1 2CDC509086D0201 115 Notes ...