ABB i-bus
®
KNX
Parameters
ABA/S 1.2.1 | 2CDC509086D0201 49
7.10.9
1ofN (ONE-HOT)
Description
Logical 1ofN link.
Inputs
No.
DPT
Abbr.
Name
Visible
Description
1
1 bit
I
1
Input
Always
2
1 bit
I
2
Input
Always
3-16
1 bit
I
n
Input
Parametrizable
n = 3...16
Outputs
No.
DPT
Abbr.
Name
Visible
Description
1
1 bit
O
Output
Always
Note
You can invert 1-bit inputs and outputs by double-clicking on the relevant I/O.
Parameters
Name
Value
Visible
Description
Input Count
2...16
Always
Function
Whenever a telegram is received the output starts a recalculation independently if the value has changed.
The output is (1) if exactly one input is true (1).
I
1
I
2
I
3
O
0
0
0
0
0
0
1
1
0
1
0
1
0
1
1
0
1
0
0
1
1
0
1
0
1
1
0
0
1
1
1
0