Parameters
ABA/S 1.2.1 | 2CDC509086D0201 73
Function
•
Input receives a 1 (true):
o
Output = 1 (true)
o
Timer restarts
•
Input receives a 0 (false):
o
Output = 0 (false)
o
Timer stops
•
If the timer reaches the On-time:
o
Output = 0 (false)
o
Timer stops
•
Retrigger:
•
If Retrigger = 1 (true):
o
When the input receives a 1 the timer restarts
•
If Retrigger = 0 (false):
o
If the timer is running and the input receives a 1 (true) it ignores it. The timer continues running.
Exception handling
•
If the
On-time
input is unlinked, the element uses 00:00:30.
•
If the
On-time
input is negative, the element uses 00:00:00.
•
If the
On-time
input has a value of 00:00:00, the output is always 0.
Bus voltage failure, download and restart
The internal timer value is saved. This value is restored on restart.