Mounting 

 

20 FSM4000 

D184B140U02 

 

 

4 Mounting 

 

 

4.1 General 

information on installation 

 

The following points must be observed for the installation: 
•  The flow direction must correspond to the identification if present. 
•  The maximum torque for all flange connections must be complied with. 
•  The devices must be installed without mechanical tension (torsion, bending). 
•  Install flange and wafer units with coplanar counter flanges and use only appropriate 

gaskets. 

•  Use only gaskets made from a compatible material for the fluid and fluid temperature or use 

only gasket material compatible with hygienic designs. 

•  Gaskets must not extend into the flow area since possible turbulence could influence the 

device accuracy. 

•  The pipeline may not exert any unallowable forces or torques on the device. 
•  Do not remove the plugs in the cable connectors until you are ready to install the electrical 

cable. 

•  Make sure the gaskets for the housing cover are seated properly. Carefully seal the cover. 

Tighten the cover fittings. 

•  Install the separate transmitter at a largely vibration-free location. 
•  Do not expose the transmitter to direct sunlight. Provide appropriate sun protection as 

necessary. 

 

 

4.2 

Supports for nominal diameters larger than DN 350 

 

 

Notice - Potential damage to parts! 

Improper support for the device may result in deformed housing and damage to internal 
magnet coils. 
Place the supports at the edge of the housing (see arrows in the figure). 

 
Devices with a nominal diameter larger than DN 350 must be mounted with support on a 
sufficiently strong foundation. 

 

 

G00462

 

Fig. 10: Support for nominal diameters larger than DN 350 

Содержание FSM4000-SE41F

Страница 1: ...Operating Instruction D184B140U02 Electromagnetic Flowmeter FSM4000 Valid for software versions C 10 and higher Model FSM4000 SE41F FSM4000 SE21 FSM4000 SE21F FSM4000 S4 ...

Страница 2: ...ttingen Germany Tel 49 551 905 0 Fax 49 551 905 777 Phone 49 180 5 222 580 automation service de abb com Copyright 2018 by ABB Automation Products GmbH Subject to changes without notice This document is protected by copyright It assists the user in safe and efficient operation of the device The contents of this document whether whole or in part may not be copied or reproduced without prior approva...

Страница 3: ...evice designs 17 3 Transport 18 3 1 Inspection 18 3 2 General information on transport 18 3 3 Transport of flanged units up to nominal diameter DN 300 18 3 4 Transport of flanged units larger than nominal diameter DN 350 19 4 Mounting 20 4 1 General information on installation 20 4 2 Supports for nominal diameters larger than DN 350 20 4 3 Mounting the meter tube 21 4 4 Torque information 22 4 4 1...

Страница 4: ...e unit 49 6 2 1 Switching on supply power 49 6 2 2 Device configuration 49 6 3 Easy Set up For uncomplicated configuration 51 6 4 Commissioning PROFIBUS PA units 52 6 4 1 Information on voltage current consumption 54 6 4 2 System integration 55 6 5 Commissioning FOUNDATION Fieldbus units 56 7 Parameterization 58 7 1 Display options 58 7 2 Data entry 59 7 3 Entering data in short form 61 7 4 Additi...

Страница 5: ...erminal box aluminum DN 3 DN 1000 111 11 Operating S4 with an older sensor 112 12 Specifications 115 12 1 Measuring accuracy 115 12 1 1 Reference conditionsper EN 29104 115 12 1 2 Maximum measuring error 115 12 2 Flowmeter sensor 116 12 2 1 Flowmeter sensor SE41F 116 12 2 2 Flowmeter sensor SE21 SE21F 119 12 3 Transmitter S4 121 13 Appendix 122 13 1 Other applicable documents 122 13 2 Approvals an...

Страница 6: ... existing agreement promise or legal relationship nor is it intended to change the same This product is built based on state of the art technology and is operationally safe It has been tested and left the factory in perfect working order from a safety perspective The information in the manual must be observed and followed in order to maintain this state throughout the period of operation Modificat...

Страница 7: ...arts Removing material e g by spot drilling the housing 1 4 Target groups and qualifications Installation commissioning and maintenance of the product may only be performed by trained specialist personnel who have been authorized by the plant operator to do so The specialist personnel must have read and understood the manual and comply with its instructions Prior to using corrosive and abrasive ma...

Страница 8: ...eath or severe injury WARNING Bodily injury This symbol in conjunction with the signal word Warning indicates a potential electrical hazard Failure to observe this safety information may result in death or severe injury CAUTION Minor injury This symbol in conjunction with the signal word Caution indicates a possibly dangerous situation Failure to observe this safety information may result in minor...

Страница 9: ...flowmeter sensor or transmitter see nos 1 or 2 in the description of the name plates can be found on the name plate The connection diagram for the respective model is contained in the section Terminal connection diagrams Technical data material load curves etc are organized by model in the section Technical data 2 Identifying the transmitter design The transmitter design can be identified from the...

Страница 10: ...ion 10 Phase relationship between signal and reference voltages 11 Reference voltage 12 Cs calibration factor span 13 Cz calibration factor zero point Transmitter ABB Automation Products GmbH 37070 Göttingen Germany S4 0002238521 Y001 U fnenn 85 253 V AC 50 60 Hz 45 VA G00524 Signal converter S4 Model No Order No Power supply Pulse output Communication Smax passive HART Comment do not connect to E...

Страница 11: ...as per the pressure equipment directive PED Fluid group 1 hazardous liquids gaseous 6 Manufacturer of the pressure equipment Pressure equipment outside the applicable range of the PED S Nr 0012345 DN 50 PN 40 Material 1 4571 PTFE Manufactured 2002 PED SEP ABB Automation Products GmbH 37070 Göttingen Germany Hast C 4 G00003 Fig 5 The factory tag contains most of the specifications included on the p...

Страница 12: ...lange and wafer type units with coplanar counter flanges Only install devices for the intended operating conditions and with suitable seals Secure the flange bolts and nuts against pipeline vibrations 1 8 Electrical installation safety information The electrical connection may only be performed by authorized specialists according to the electrical plans Comply with electrical connection informatio...

Страница 13: ...erature TS may not exceed the pressure temperature ratings The maximum operating temperature may not be exceeded The permitted operating temperature may not be exceeded The housing protection system must be observed The flowmeter sensor may not be operated in the vicinity of powerful electromagnetic fields e g motors pumps transformers etc A minimum spacing of approx 1 m 3 28 ft should be maintain...

Страница 14: ...ing items through a regular inspection the pressure carrying walls lining of the pressure device the measurement related function the leak tightness the wear corrosion 1 13 Returning devices Use the original packaging or suitably secure shipping containers if you need to return the device for repair or recalibration purposes Fill out the return form see the Appendix and include this with the devic...

Страница 15: ...s an open dialog with the public through our publications 1 15 Disposal This product is manufactured from materials that can be reused by specialist recycling companies 1 15 1 Information on WEEE Directive 2012 19 EU Waste Electrical and Electronic Equipment This product is not subject to WEEE Directive 2012 19 EU or relevant national laws e g ElektroG in Germany The product must be disposed of at...

Страница 16: ...proportional to the magnetic induction B the electrode spacing D and the average flow velocity v Considering that the magnetic induction B and the electrode spacing D are constant values a proportionality exists between the signal voltage UE and the average flow velocity v From the equation for calculating the volume flowrate it follows that the signal voltage is linearly proportional to the volum...

Страница 17: ...For flowmeters with preamplifiers the signal length is increased to 200 m The electrical connection between the transmitter and the flowmeter sensor is provided by a signal cable and a magnet coil cable in the terminal box Fig 7 The transmitter is available in the design Field housing unit model S4 The flowmeter sensor comes with aluminum or stainless steel housing Aluminum housing Model FSM4000 S...

Страница 18: ...y only be removed before installation To prevent possible leakage make sure that the liner is not cut or damaged Flanged units may not be lifted by the transmitter housing or terminal box 3 3 Transport of flanged units up to nominal diameter DN 300 Warning Danger of injuries due to slipping meter The center of gravity of the complete meter may be higher than the lifting straps Make sure the device...

Страница 19: ... and damage the internal magnet coils Flanged units must not be lifted by the center of the housing when using a forklift for transport Flanged units must not be lifted by the terminal box or by the center of the housing Only the eyebolts fitted to the meter must be used to lift the meter and set it down in the pipeline G00461 Fig 9 Transport of flanged units larger than nominal diameter DN 350 ...

Страница 20: ...y The pipeline may not exert any unallowable forces or torques on the device Do not remove the plugs in the cable connectors until you are ready to install the electrical cable Make sure the gaskets for the housing cover are seated properly Carefully seal the cover Tighten the cover fittings Install the separate transmitter at a largely vibration free location Do not expose the transmitter to dire...

Страница 21: ...nt possible leakage make sure that the liner on the flange is not cut or damaged 2 Position the meter tube coplanar and centered between the pipes 3 Install gaskets between the surfaces Important Ideally flowmeter sensors with PTFE PFA or ETFE linings should be installed without gaskets For best results make sure the flowmeter sensor gaskets fit concentrically with the meter tube 4 Use the appropr...

Страница 22: ... 14 68 14 68 20 3 4 PN40 9 78 7 27 20 75 20 75 PN63 100 24 57 20 42 42 15 42 15 CL150 5 29 5 29 18 49 18 49 CL300 9 77 9 77 33 28 33 28 CL600 15 99 15 99 JIS 10K 4 1 1 88 20 75 20 75 25 1 PN40 13 32 8 6 13 32 8 6 PN63 100 32 09 31 42 53 85 53 85 CL150 5 04 2 84 23 98 23 98 CL300 17 31 16 42 65 98 38 91 CL600 22 11 22 11 JIS 10K 8 46 5 56 26 94 26 94 32 1 1 4 PN40 27 5 15 01 45 08 45 08 PN63 100 42...

Страница 23: ...150 19 46 19 46 104 6 104 6 CL300 75 54 26 91 75 54 75 54 CL600 84 63 84 63 JIS 10K 16 26 9 65 45 07 47 16 100 4 PN16 20 7 12 22 49 68 78 19 PN40 67 77 47 12 78 24 78 19 PN63 107 4 95 79 148 5 119 2 CL150 17 41 7 82 76 2 76 2 CL300 74 9 102 6 102 6 102 6 CL600 147 1 147 1 JIS 10K 20 7 12 22 49 68 78 19 125 5 PN16 29 12 18 39 61 4 64 14 PN40 108 5 75 81 123 7 109 6 PN63 180 3 164 7 242 6 178 2 CL15...

Страница 24: ... 282 3 204 3 226 9 167 9 CL150 144 8 83 9 270 5 263 CL300 424 1 252 7 463 9 259 4 400 16 PN10 108 2 75 61 120 1 113 9 PN16 189 137 2 191 4 153 8 PN25 399 4 366 404 246 7 CL150 177 6 100 229 3 222 8 CL300 539 5 318 8 635 8 328 1 450 18 CL150 218 6 120 5 267 3 192 3 CL300 553 8 327 2 660 9 300 500 20 PN10 141 6 101 4 153 9 103 5 PN16 319 7 245 4 312 1 224 8 PN25 481 9 350 5 477 1 286 CL150 212 5 116...

Страница 25: ...0 387 7 296 3 On request On request PN16 680 8 537 3 On request On request PN25 1399 1119 On request On request CL150 336 2 394 6 511 458 5 CL300 1972 On request On request On request 1000 40 PN10 541 3 419 2 On request On request PN16 955 5 756 1 On request On request PN25 2006 1612 On request On request CL150 654 2 598 8 650 6 385 1 CL300 2181 On request On request On request 4 4 2 Variable proc...

Страница 26: ...tter housing pointing upward The bracket mounting 1 option no longer applies G00528 01 1 Fig 12 If concentric reducers are installed on the device it must be mounted in a vertical position Refer to the section 4 6 9 Installation in pipelines with larger nominal diameter G00991 Fig 13 Please ensure that the leakage hole of the process connection is located at the deepest point of the installed devi...

Страница 27: ...ed in the outlet pipe section 2 Experience has shown that in most installations straight inlet sections 3 x DN long and straight outlet sections 2 x DN long are sufficient DN nominal diameter of the sensor Fig 17 For test stands the reference conditions of 10 x DN straight inlet and 5 x DN straight outlet must be provided in accordance with EN 29104 ISO 9104 G00983 1 2 2xDN 3xDN Fig 17 4 6 3 Verti...

Страница 28: ...after installing the unit according to the following illustration G00976 1 Fig 23 1 Insulation 4 6 9 Installation in pipelines with larger nominal diameter Determine the resulting pressure loss when using reduction pieces 1 1 Calculate the diameter ratio d D 2 Determine the flow velocity based on the flow range nomograph Fig 25 3 Read the pressure drop on the Y axis in Fig 25 G00989 1 D d 8 Fig 24...

Страница 29: ...n 53 106 159 US gal min US gal min US gal min 50 65 80 2 2 1 2 3 40 40 40 0 0 0 3 6 9 m3 h m3 h m3 h 13 26 40 US gal min US gal min US gal min 0 0 0 60 120 180 m3 h m3 h m3 h 264 528 793 US gal min US gal min US gal min 100 125 150 4 5 6 16 16 16 0 0 0 12 21 30 m3 h m3 h m3 h 53 92 132 US gal min US gal min US gal min 0 0 0 240 420 600 m3 h m3 h m3 h 1057 1849 2642 US gal min US gal min US gal min...

Страница 30: ...al An additional ground via the terminals is not required Important If the flowmeter sensor is installed in plastic or earthenware pipelines or in pipelines with an insulating lining transient current may flow through the grounding electrode in special cases In the long term this may destroy the flowmeter sensor since the ground electrode will in turn degrade electrochemically In these special cas...

Страница 31: ...h insulating liner For plastic pipes or pipes with insulating lining the ground for the measuring agent is provided by the grounding plate as shown in the figure below or via grounding electrodes that must be installed in the device option If grounding electrodes are used the grounding plate is not necessary 1 Install the flowmeter sensor with grounding plate 1 in the pipeline 2 Insert M6x12 threa...

Страница 32: ...he protective plates are used to protect the edges of the liner in the measuring tube e g for abrasive fluids In addition they function as a grounding plate For plastic or pipes with insulating lining electrically connect the protective plate in the same manner as a grounding plate 4 8 7 Ground with conductive PTFE grounding plate For devices with a meter size between DN 10 250 grounding plates ma...

Страница 33: ...able D173D147U01 Preparing the transmitter side G00535 15 5 30 1 18 8 8 80 3 15 60 2 36 0 20 0 59 17 0 67 0 31 17 0 67 0 31 Preparing the flowmeter sensor side G00549 5 4 3 2 1 G00552 M1 M3 1 2 3 Cable identifiers Fig 30 Dimensions in mm inch 1 Measurement potential yellow 2 Reference white 3 Signal cable red 4 Signal cable blue 5 SE clamp 1 Magnet coil black 2 Magnet coil black 3 SE clamp Importa...

Страница 34: ...or switching elements that can create stray fields switching pulses and induction If this is not possible run the signal magnet coil cable through a metal pipe and connect this to the station ground All leads must be shielded and connected to station ground Do not run the signal cable and the magnet coil cable over junction boxes or terminal blocks To shield against magnetic interspersion the cabl...

Страница 35: ...S 1 2 3 16 16 M1 M3 1 2 3 6 5 7 4 6 9 8 G00554 SE SE 3A 3A U U 1 2 3 16 16 M1 M3 1 2 3 6 5 7 4 6 9 8 Terminal box without preamplifier Terminal box with preamplifier Fig 32 1 red 2 blue 3 yellow 4 white 5 black 6 SE clamp 7 Signal cable 8 Grounding screw 9 Magnet coil cable 1 red 2 blue 3 yellow 4 white 5 black 6 SE clamp 7 Signal cable 8 Grounding screw 9 Magnet coil cable Terminal designation Co...

Страница 36: ...able to connect the flowmeter sensor and the transmitter 2 Connect the signal cable in the terminal box of the sensor 3 Route the cable from the terminal box to above the maximum flooding height of 5 m 16 4 ft 4 Tighten the cable gland 5 Carefully seal the terminal box Make sure the gaskets for the cover are seated properly Warning Potentially adverse effect on IP 68 protection class The sensor s ...

Страница 37: ...ies in order avoid moisture penetration Before starting check all the connections for correct fitting and stability Do not overfill the terminal box Keep the sealing compound away from the O ring and the seal groove see Fig 34 Prevent the sealing compound from penetrating a thermowell if an NPT thread is used Procedure 1 Cut open the protective enclosure of the sealing compound see packaging 2 Ope...

Страница 38: ...ption of the flowmeter system The leads must comply with IEC 227 and or IEC 245 Connect a switch or a line switch in the power supply line to the transmitter This switch should be located near the converter and marked as being associated with the device The transmitter and the flowmeter sensor have to be connected to functional ground in accordance with international standards Important Please obs...

Страница 39: ...ignal cable 2 Magnet coil cable 3 Busbar SE Important The power supply of the FSM4000 with preamplifier is connected via U and U instead of 1S and 2S If the flow indicator shows the incorrect direction after successful startup of the meter e g reverse instead of forward correct this in the Operating Mode submenu of the transmitter First switch off the Programming Protection Prog Level Specialist T...

Страница 40: ...shielded 2 x 1 mm2 CE Typ 227 TEC 74 ABB order no D173D147U01 10 m included in shipment standard 7 Supply power Low voltage 100 230 V AC terminals L N Low voltage 20 4 26 4 V AC Low voltage 20 4 31 2 V DC Low voltage Terminals 1 2 Frequency 47 Hz f 53 Hz 50 Hz supply power Frequency 56 Hz f 64 Hz 60 Hz supply power 8 Steel shielding 9 Aluminum foil 10 Yellow 11 Shield 12 Blue 13 Red 14 White 15 Sh...

Страница 41: ...s L N Low voltage 20 4 26 4 V AC Low voltage 20 4 31 2 V DC Low voltage Terminals 1 2 Frequency 47 Hz f 53 Hz 50 Hz supply power Frequency 56 Hz f 64 Hz 60 Hz supply power 8 Steel shielding 9 Aluminum foil 10 Yellow 11 Shield 12 Blue 13 Red 14 White 15 Shielded signal cable ABB order no D173D025U01 10 m included in shipment 16 With preamplifier always with DN 1 DN 8 1 25 5 16 1 See the section Con...

Страница 42: ...Contact output1 5 Current output1 6 Supply power Low voltage 100 230 V AC terminals L N Frequency 47 Hz f 53 Hz 50 Hz supply power Frequency 56 Hz f 64 Hz 60 Hz supply power 7 Shielded signal cable Use ABB order no D173D025U01 or incorporate in existing wiring 8 Reference cable Only for connection to model 10D1422 Terminals close 6 7 and the hook switch S903 9 Magnet coil supply Magnet coil supply...

Страница 43: ...ection Connecting via M12 plug in the operating 3a instructions and or on the data sheet 3c Bus termination with installed bus termination 3a components with hook switches closed 4 Magnet coil cable shielded 2 x 1 mm2 CE Typ 227 TEC 74 ABB order no D173D147U01 10 m included in shipment standard 5 Supply power Low voltage 100 230 V AC terminals L N Low voltage 20 4 26 4 V AC Low voltage 20 4 31 2 V...

Страница 44: ... I E 0 V 24 V DC Note Horn and alarm light are shown only as examples Other suitable devices such as bells sirens buzzers etc can also be used Contact output selectable in software Function Passive closed 0 V UCEL 2 V 2 mA ICEL 220 mA open 16 V UCEH 30 V 0 mA ICEH 2 mA Terminals 41 42 Fig 41 Contact output for system monitoring Max Min alarm for empty tube or forward reverse signal Contact input G...

Страница 45: ...ulse width 50 ms max pulse frequency 3 Hz 500 Ω Load 10 kΩ Pulse width 0 1 ms max pulse frequency 5 kHz Passive closed 0 V UCEL 2 V 2 mA ICEL 220 mA open 16 V UCEH 30 V 0 mA ICEH 2 mA Terminals 51 52 Fig 43 Pulse output active and passive optocoupler PROFIBUS PA FOUNDATION Fieldbus G00248 2 FF FF R C 1 97 PA R C PA 98 97 98 I E I E The resistance R and capacitor C form the bus termination They mus...

Страница 46: ...49 M3 M1 41 42 97 98 U 2S 1 1S U 3 3 2 16 6 7 Connection board for field housing unit Hook switches for bus termination must be closed Fig 45 Connection via M12 plug for PROFIBUS PA only As an option the bus can also be connected via an M12 plug instead of the cable gland see order information for device The device can be shipped completely prewired For information about suitable connectors type E...

Страница 47: ...ata module stores the sensor data e g size Cs Cz type etc as well as the setup data on the transmitter after commissioning Prior to commissioning plug the external FRAM for the appropriate sensor order no is printed on the FRAM and if available a TAG no to the connection board for the installed transmitter Then screw to the connection board captive G00558 1 1 Fig 47 1 External FRAM Important If a ...

Страница 48: ...ters have the end numbers Y1 Y2 etc End numbers X1 and Y1 are considered a unit Monitoring of pulse output The pulse output can be operated as active output 24 VDC pulse or as passive output optocoupler The current setting is provided on the name plate for the transmitter Modification as shown in the following illustration G00559 1 A B Fig 48 Setting the pulse output using jumpers 1 Display board ...

Страница 49: ...kly and conveniently see chapter 6 3 Easy Set up For uncomplicated configuration The following parameters should be checked or set before start up 1 Flow range end value menu items Qmax and Unit The devices factory setting is largest flow range end value unless other customer information is available The ideal flow range end values are approximately 2 3 m s First set the unit Qmax e g m3 h or l s ...

Страница 50: ... and or without preamplifier When the DEP mode Standard is selected it is not required to perform an adjustment onsite The transmitter works with standard setup data If the function is not performed correctly a new adjustment must be run with the fluid onsite The adjustment can be made with a full or empty meter pipe 8 Extended diagnostic functions To measure the DC resistance or the coil temperat...

Страница 51: ...max l s Unit totalizer m3 Qmax 50 000 l s Damping 1 Tau 0 22 sek Display mode 4 small Display 1st line Q Unit Display 2nd line Display 4th line Display 3rd line Within Easy Set up call up the next parameter using the C CE key Change the parameter using the Enter function m s Q Pulse width 0 1000 ms Pulse factor 1 m3 lout High Alarm 23 000 mA lout Low Alarm 3 6 mA Iout at Alarm High Alarm Totalizer...

Страница 52: ...the DIP switches on the digital board using system tools or via a PROFIBUS DP master class 2 such as Asset Vision Basic DAT200 The factory setting for DIP switch 8 is OFF i e the address is set using the fieldbus The front cover can be unscrewed to change the settings It is also possible to set the address via menu by using the keys on the display board The PROFIBUS PA interface conforms with Prof...

Страница 53: ...witches 1 5 7 ON means 1 16 64 81 Bus address 81 Switch 1 2 3 4 5 6 7 8 9 A Status Unit address Address mode no function no function Off 0 0 0 0 0 0 0 Bus no function no function On 1 2 4 8 16 32 64 Local no function no function Switch assignments Switch Assignment 1 7 PROFIBUS address 8 Defines the addressing mode Off Set address via bus factory setting On Set address via DIP switches nos 1 7 ...

Страница 54: ...n is activated via both hook switches the bus termination is canceled when the transmitter plug in module is removed The bus is no longer terminated properly To ensure proper operation the bus termination must be connected at another location If the transmitter plug in module is reinstalled the old bus termination can be used again Important The selector is preconfigurd with the ID no 0x078C hex T...

Страница 55: ... system Users decide at system integration whether to install the full range of functions or only part Important Units are interchanged using the parameter ID number selector which can only be modified on an acyclical basis The following table describes the available GSD files Number and type of function blocks ID number GSD file name 1 x AI 0x9700 PA139700 gsd 1 x AI 1 x TOT 0x9740 PA139740 gsd 1...

Страница 56: ...e available to download from the ABB homepage http www abb com flow The DIP switches on the unit must be set correctly as follows DIP switch 1 must be OFF DIP switch 2 must also be OFF Otherwise the hardware write protection and the process control system prevent the unit from recording information The FOUNDATION fieldbus interface for the unit is compliant with the standards FF 890 891 and FF 902...

Страница 57: ...ress settings The bus address is automatically allocated at the FF via LAS link active scheduler For address detection a unique number is used DEVICE_ID This number is a combination of manufacturer ID device ID and device serial number The behavior when switching on the unit corresponds to Draft DIN IEC 65C 155 CDV of June 1996 The average current draw of the unit is 10 mA The voltage on the bus l...

Страница 58: ...ex mode Totalizer overflow always occurs at a value of 9 999 999 units If the totalizer value for a flow direction is larger than 9 999 999 units Warning 9 is displayed in the 4th line The totalizer software can register up to 250 overflows The overflow notification can be cleared in the Reset totalizer submenu Error condition When an error occurs an error or warning message appears in the 4th lin...

Страница 59: ...the individual keys are explained in the following C CE Toggle between operating mode and menu STEP The STEP key is one of two arrow keys Use STEP to scroll forward through the menu All the desired parameters can be called up DATA The DATA key is one of two arrow keys Use DATA to scroll backward through the menu All the desired parameters can be called up ENTER The ENTER function requires that bot...

Страница 60: ...r more than 3 seconds The display flashes to indicate that the function is active There are two different methods of entering data Numeric entry Entry from specified table Important When entering data the values are checked for plausibility and if necessary rejected with an appropriate message The limit values min max are displayed in the 3rd and 4th lines ...

Страница 61: ...Qmax 5 Parameter Submenu unit STEP or DATA Submenu 1800 00 m h Unit 6 Change parameter Qmax ENTER Qmax 6 Change parameter m h ENTER Unit Qmax m h m h Min 500 m h Max 10000 m h 7 Find desired value e g m min STEP or DATA Unit Qmax m min Qmax 6 2 4 0 0 0 m h 8 Set value ENTER Unit Qmax 7 Enter the desired value in the sequence 6 x DATA STEP 2 x DATA STEP 4 x DATA STEP STEP 10 x DATA STEP STEP m min ...

Страница 62: ... the PP Code menu Select ENTER and you will be asked for the old PP code You must enter the correct old code before the message New PP Code is displayed Enter a new code or select 0 to disable the PP Code function 0 New Pg prot code 1 9999 0 Submenu Language Unit Qv Unit Zv Qmax Damping 1 000 Display mode Display line 1 Display line 2 Display line 3 Display line 4 Iout Art Iout Alarm Low Alarm Hig...

Страница 63: ...tandard inverse reverse the flow direction indicators in the display for forward and reverse flow Standard Noise reduction Off 1 2 3 4 The noise reduction is switched on when the measured value is very unstable or temporarily or permanently frozen error E Note Activating noise reduction increases the response time Off Flow direction Forward Reverse Forward When the flow indication Forward Reverse ...

Страница 64: ...ers default value in kgal units factory setting 3785 1 Prog Unit Without density With density Unit for mass with density or volume without density without density Density Numeric entry Density range 0 1 5 g cm3 Mass flowrate for display and totalization The density is only considered when mass flow units are and or totalizer mass units are selected 1 g cm3 Submenu System data Submenu Converter Sub...

Страница 65: ...ted 91 Submenu This menu does not appear with an excitation frequency of 50 Hz or 60 Hz Data 70 Hz Channel View only Adjustment value for Channel can be monitored for the excitation frequency setting displayed when a new sensor has been selected 123 µs Zero View only Adjustment value for Zero can be monitored for the excitation frequency setting displayed when a new sensor has been selected 0 Span...

Страница 66: ... displayed at initial startup Additional settings can be entered in the system data submenu Primary See chapter 11 DS2_ DS4 Frequency View only Display the mains frequency for which the flowmeter sensor was calibrated Displayed only for 50 60 Hz older models Not displayed if new flowmeter sensor is selected 50 Hz Meter size View only 1 mm 1 25 in 1 5 mm 1 17 in 2 mm 1 12 in 3 mm 1 10 in 4 mm 5 32 ...

Страница 67: ...P to access the parameters Mains Frequency Type of Sensor Meter Size and Reference Voltage Not displayed if new sensor SE41F SE21 is selected See chapter 11 Primary Setup Frequency 50 60 Hz Displays the mains frequency for the flowmeter sensor Option available only with new Flowmeter sensor 50 Hz Type of primary Select the original model Display the connected flowmeter sensor model DS4_ Meter size...

Страница 68: ...vel drops below the electrode level all outputs can be automatically set to zero This ensures false pulses or incorrect displays are avoided when the meter pipe is empty In addition to the message in the display this condition can be reported via the switch contact output If the meter pipe is filled the error message empty pipe is turned off and the meter returns to normal operation Detector e pip...

Страница 69: ...nt values full and empty are determined and the threshold based on these values is optimized the transmitter always uses only the most recent adjustment value The threshold value is the basic criteria used for the DEP function The adjustment values are used only to calculate the threshold Not displayed if DEP is switched off or DEP mode is standard 100000 Alarm e pipe Off If the alarm is switched ...

Страница 70: ...Flow Transducer block Index 17 TB VolFlow Value 1st line TB VolFlow Status Displays the status of Volume_Flow Transducer block Index 17 TB VolFlow Status 1st line TB Total F Value Displays the value for Totalizer F Transducer block Index 102 TB Total Status Displays the status of the Totalizer F Transducer block Index 102 TB Total R Value Displays the value for Totalizer R Transducer block Index 1...

Страница 71: ...Totalizer diff Detector empty pipe additional options FF address displayed in hexadecimal TBT Status 1st line Displays the value or status of the flowrate TB Primary_Value Index 14 TB VolFlowValue 1st line Displays the value or status of the Totalizer Forward TB Secondary_Value Index 28 TB Total V Value 1st line Displays the value or status of the Totalizer R TB Third_Value Index 30 TB Total R Val...

Страница 72: ...larm Min Alarm 103 of configured flow range Configurable in 1 increments 1 switching hysteresis 100 Submenu The totalizer function is set automatically in the Operating mode submenu Standard operating mode standard totalizer function Piston pump mode Totalizer function Diff totalizer Standard For the standard totalizer function the counting pulse for forward and reverse flow is registered on two s...

Страница 73: ...w Alarm High Alarm Behavior of the current output during an alarm Low Alarm is available only for current output of 2 10 mA and 4 20 mA If error 0 empty pipe occurs the current output is set to the value programmed for the parameter lout during empty pipe in the submenu Detector empty pipe If error 3 flowrate 103 occurs High Alarm is always signaled Low Alarm Iout low alarm Numerical entry Low Ala...

Страница 74: ... totalizer and overflow values when a switching voltage is connected For Ext Zero Return all outputs are switched off if a switching voltage is connected Example Undefined filled pipeline condition after turning off pumps or cyclic cleaning or flushing procedures whose flowrates must be hidden Select Ext Syst NP to adjust the system zero point The fluid must be at absolute standstill during the ad...

Страница 75: ...e for standard devices without HART hardware None Device address Numerical entry 0 15 For devices with HART protocol an address between 0 15 can be selected If the address entered is 0 the current output varies with the flowrate in the range of 4 20 mA If multiple devices are connected to the bus and an address between 1 and 15 is assigned the transmitter runs in multidrop mode The current output ...

Страница 76: ...ay only Displays the settings for the DIP switches OFF X ON If DIP switch 8 ON The address is binary coded using switches 1 7 Switches and 9 and A have no function Example Use switches to set address 50 50dec 32hex 110010 binary DIP switches 2 5 6 and 8 to ON PA address 50 The changed address switch setting is only imported after the device is rebooted not if changed during normal operation The fa...

Страница 77: ...nk submenu It can also be read via the FF communication in the transducer block An open switch is shown as a closed switch as x The following switches are assigned Switch 1 Simulate Enable off Simulation mode disable on Simulation Mode enabled Switch 2 Write Protect Off Simulation Mode disabled on Write protect enabled Simulation mode enabled only allows you to run a simulation not to actually sta...

Страница 78: ... 0 10 mA 2 10 mA This menu does not appear for the PROFIBUS PA or FOUNDATION fieldbus Test the current output Check the value displayed at the connection terminals using a digital voltmeter or the process instrumentation Enter a value directly in mA No selection available if the HART device address is anything other than 0 4 mA Contact input Off On This menu does not appear for the PROFIBUS PA or ...

Страница 79: ...ual 10 s 60 s 10 min 60 min 6 h 12 h 24 h 7 d Select the time interval between the individual diagnostic measurements For the values for Coil Resistance Coil Temperature Insulation Resistance and Magnetic Linearity however there are minimum measurement intervals for technical reasons related to the measurement 60 seconds for Coil Resistance and Coil Temperature 5 minutes for Magnetic Linearity 10 ...

Страница 80: ...imit for alarm 2 ohms Max value 0 500 Upper range limit for alarm 500 ohms Message Off warning error Defines the alarm behavior Off Note If coil resistance is being measured at least every 60 s the most recently acquired flowrate is retained during the measurement 2 s approx Submenu Set the time out limits and alarm behavior for values over or under the coil temperature Note To correctly display t...

Страница 81: ... electrode AC voltage for electrode E1 Alarm E1 Voltage Min value 0 3000 Lower range limit for alarm 0 0 µV Max value 0 3000 Upper range limit for alarm 3000 0 µV Message Off warning error Defines the alarm behavior Off Note To properly display the electrode voltage the electrode zero must be adjusted For additional information see Submenu Adjustment on page 85 Submenu Set the time out limits and ...

Страница 82: ... the electrode voltage the electrode zero must be adjusted For additional information see Submenu Adjustment on page 85 Submenu Set the time out limits and alarm behavior for values over or under the magnetic linearity Alarm Mag Lin Min value 0 100 Lower range limit for alarm 0 0 Max value 0 100 Upper range limit for alarm 100 0 Message Off warning error Defines the alarm behavior Off Note If magn...

Страница 83: ...in alarms to the default values Alarm Factory Set Accept Yes exit via C CE Yes Enter Submenu Wiring Error Submenu Defines alarm behavior in case of an accidental coil ground CoilShtCircGnd Note If the coil circuit is being checked at least every 10 minutes for an accidental ground the most recently acquired flowrate is maintained approx 2 s Message Off warning error Off Submenu Defines alarm behav...

Страница 84: ...ity SNR Signal to noise ratio Max DAC value Max DAC value Oprtg hrs trn Operating hours for transmitter Oprtg hrs trn Operating hours for flowmeter sensor These values are updated only if the status was set to Warning or Error in the Alarm Settings submenu AC volt coil Data record Current Prod1 Prod2 Startup Factory Hist1 Hist2 Hist3 Hist4 Hist5 Hist6 Hist7 Hist8 Hist9 Current Data record for curr...

Страница 85: ...l information regarding use of enhanced diagnostic functions Note This menu is displayed only when the coil resistance or coil temperature are enabled as an error or warning message Accept Yes exit C CE New 500 ohms Old 450 ohms Yes Enter Electr Zero Point This adjustment is required in order to use the diagnostic measurement values for the electrode voltage E1 E2 and the electrode balance as well...

Страница 86: ...Empty pipe Warning register After calling up the warning register the warning register text is displayed with the number of pending warnings Press ENTER again to display the pending warnings with warning number and text If you press ENTER again you will be asked whether you want to reset the warnings or view the help text Select STEP to display all of the pending warnings with warning numbers and ...

Страница 87: ...luid in flowmeter sensor must be at absolute standstill Press ENTER to perform the automatic adjustment The limit for the zero point is 10 If the value is outside this limit no calibration is performed 0 0 FSM4000 01 2010 Display only Display software version 01 2010 specifies the date of the release C0 11 Version level for standard and HART protocol models D699G004U01 C0 11 FSM4000 PA3 0 Display ...

Страница 88: ...surements To perform the measurement it is necessary to switch on one of the relevant errors or warnings in the submenu Diagnostics Alarm Settings see page 80 7 4 1 2 Determining the coil DC resistance I U G00578b For monitoring changes in the coil circuit e g fine short of coil When measuring the coil DC resistance a DC field excitation of approx 1 sec is used as a test signal Because the incomin...

Страница 89: ...wly shipped systems SE41F SE21 and S4 When connecting an S4 transmitter to already shipped transmitters SE41F SE21 it is also necessary to perform the adjustment For additional information see chapter 7 4 4 Readjusting the coil temperature 7 4 1 4 Determining the insulation resistance for the coil G00578d Detecting problems with the coil insulation Can be caused e g by dampness in the flowmeter se...

Страница 90: ...Determining the electrode balance E1 E2 EB 2 E 1 E E1 E2 EB 1 E 2 E Detect distorted flow profile e g due to improper installation Detect interference in electrode circuit e g failure of electrode due to insulating coating or a collapsed liner vacuum shock The electrode balance EB is calculated as the ratio between the electrode AC voltages E1 E2 or E2 E1 This value is displayed in To prevent fals...

Страница 91: ...e coil current I1 is measured at current reference voltage UR1 and coil current I2 at approximately half the reference voltage UR2 The operating time at half the reference voltage is approx 1 sec During this period the most recently acquired value is retained To perform this test it is necessary to switch on one of the relevant errors or warnings in the submenu Diagnostics Alarm Settings see page ...

Страница 92: ...ory fingerprint x 1 16 90 C 194 F Factory fingerprint x 1 14 90 C 194 F Factory fingerprint x 1 26 130 C 266 F Factory fingerprint x 1 24 130 C 266 F Factory fingerprint x 1 37 180 C 356 F Factory fingerprint x 1 33 180 C 356 F Factory fingerprint x 1 47 Coil resistance This value depends on the fluid temperature Tmedium Tmedium Tmedium 40 C 40 F Factory fingerprint 0 71 40 C 40 F Factory fingerpr...

Страница 93: ...Tmedium Tmedium Tmedium 40 C 40 F Factory fingerprint x 0 86 40 C 40 F Factory fingerprint x 0 95 20 C 4 F Factory fingerprint x 0 90 20 C 4 F Factory fingerprint x 1 0 C 32 F Factory fingerprint x 0 93 0 C 32 F Factory fingerprint x 1 03 20 C 68 F Factory fingerprint x 0 95 20 C 68 F Factory fingerprint x 1 05 60 C 140 F Factory fingerprint x 1 60 C 140 F Factory fingerprint x 1 10 90 C 194 F Fac...

Страница 94: ...esult each line appears as follows e g CV_RCL 80 5 ohm for the current coil resistance CV _ RCL 80 5 ohm Data record Type Numerical value Unit CV_ Current value UAC Coil voltage AC X X V H1_ History 1 IAC Coil current AC X mA H2_ History 2 RCL Coil resistance Value 100 X Value 100 X X Ohm H3_ History 3 TCL Coil temperature X C H4_ History 4 RIS Insulation resistance Value 100 X Value 100 X X MOhm ...

Страница 95: ...nt flowmeter sensor log time H Min Sec FVP Factory Fingerprint flowmeter sensor log time H Min Sec H1P H9P History 1 9 flowmeter sensor log time H Min Sec 7 4 3 2 Diagnostic warning and error messages All values acquired during diagnostics or a wiring error can trigger warnings or error messages Warnings are displayed in the fourth line only In the event of an error the contact output may as an op...

Страница 96: ...ndershot while transmitter is in operation EMx Curr Max Errors Error Max present available current overshoots EMi Curr Min Errors Error Min present available current undershoots WMx Curr Max Warn Warning Max present available current overshoots WMi Curr Min Warn Warning Min present available current undershoots The information EMx _R______B__ indicates Max Alarm in the current values for the coil ...

Страница 97: ...vely close to ambient temperature You might need to allow the flowmeter to cool off overnight Work steps Switch on the transmitter Under Diagnostics Adjustment CabLength enter or check the cable length Enter the ambient temperature in the submenu Diagnostics Adjustment Coil Temp Store the new reference resistance in the submenu Diagnostics Adjustment Transfer RT20 ...

Страница 98: ... language Added error E DC too high Updated flowmeter sensor 10D1462 72 Added documentation for the additional points B0 22 Always display the flowrate with 4 decimal places B0 30 Menu item for noise reduction Menu item Meter factor Support for flowmeter sensors SE21 DN 1 DN 2 Added documentation for the additional points B0 31 Hardware compatibility for C level hardware B0 32 Improved totalizer m...

Страница 99: ...ic functions etc Added documentation for the additional points C0 12 Improved PA stack C0 13 Improved support for older flowmeter sensor 7 5 3 For transmitter with FOUNDATION Fieldbus communication Software D200S021U03 Software version Type of changes Documentation Supplements B0 14 Original Software B0 15 Improved FF stack C0 10 Extended diagnostic functions etc Added documentation for the additi...

Страница 100: ...verter DSP 0 Prog Al 0 Alarm Trans Mal F 2 Driver 0 Prog Al 0 Alarm Trans Mal F 3 Flow 103 103 Yes High Al 103 Alarm PV out Limits 4 Zero return 0 0 0 Alarm More Stat avai 5 Data base 0 Yes Prog Al 0 Alarm Trans Mal F 6 Totalizer Yes Alarm More Stat avai A Max Alarm Yes Alarm Alarm Alarm More Stat avai B Min Alarm Yes Alarm Alarm Alarm More Stat avai C Ext data base 0 Yes Prog Al 0 Alarm Trans Mal...

Страница 101: ...rd Error 2 Driver 7 Positive or negative reference too small Check the cables no reference voltage is present The current limiter in the driver has responded because the driver current is insufficient Defective driver fuse Check connection board and transmitter Error 3 Flow 103 6 The max measuring range was exceeded by more than 3 The flowrate is set too high or the measuring range is set too smal...

Страница 102: ...signal Empty pipe Activate Noise reduction in the operating mode submenu Use a air separator clean electrodes activate empty pipe detector Contact ABB Service Error F FRAM in Primary 1 Missing data from external FRAM FRAM for the flowmeter sensor is still installed in the terminal box Install and screw in place the FRAM for the associated flowmeter sensor to the connection board in the field housi...

Страница 103: ...cognized different flowmeter sensor data and loaded it in the internal FRAM Loaded are the system and flowmeter sensor data Defective FRAM repair unit replace instrument Write down all totalizer values totalizers should be reset Warning 8a1 Update int Dat 10 Transmitter has detected an error in the internal FRAM and has repaired the data with content of the external FRAM Defective FRAM repair unit...

Страница 104: ...with a counter Simulation pulse output on Exit the functional test of the pulse output Warning 132 3 Auto Adjust 15 Adjustment started for system zero point adjustment via the contact input for internal adjustment for ABB Service only The external contact is closed For ABB Service personnel only The external contact is open again For ABB Service personnel only Warning 14 Hold MV 16 Warning results...

Страница 105: ...ctrodes must be cleaned when the flowrate information on the transmitter changes when recording the identical flowrate volume If the display shows a higher flowrate the contamination is insulating If the flowrate displayed is lower the contamination results in a short circuit For repairs to the lining electrodes or magnet coil the flowmeter must be returned to the local office of ABB Important Whe...

Страница 106: ... switches the bus termination is canceled when the transmitter plug in module is removed The bus is no longer terminated properly Warning Electrical voltage risk When the housing is open EMC protection is impaired and protection against contact is suspended Power to all connecting cables must be switched off 1 Switch off the supply power before installing the replacement transmitter plug in After ...

Страница 107: ...l configuration data the process data is imported from the internal to external FRAM The flowmeter sensor data continues to be imported from the external to internal FRAM The following message is displayed Warning 8b Update external FRAM If the external data cannot be loaded in scenarios a to d the program attempts to repair the defective data The following messages may be displayed Warning 8a Upd...

Страница 108: ... minutes remove the housing cover from the field housing unit 2 To replace the fuses for the remove the protective cover 1 loosen and remove the 3 screws 2 G00579 1 2 G00581 4 5 3 Fig 54 1 Protection cover 2 Screws for cover 3 Pre fuse for supply power on the backplane 4 Fuse for supply power on the transmitter electronic unit 5 Fuse for driver circuit on the backplane Parameter Order number 3 Pre...

Страница 109: ...on board PA FF D685A1020U03 D685A1020U02 3 Cover large complete D641A030U01 4 PVC cover D626A005U01 5 Spacer bolts M4 x 75 galvanized steel D124E009U20 6 Cover small D641A029U01 7 Connection diagram standard HART Connection diagram PROFIBUS PA FF D338D311U01 D338D311U02 8 Flat cable holder D174D002U03 9 Field housing unit empty D641A033U01 10 Cable gland M 20 x 1 5 D150A008U15 11 Pan head Phillips...

Страница 110: ... board standard DN 8 D685A1025U01 1 1 Connection board with preamplifier D685A1028U01 2 Lower section SS 1 4301 model SE21_ D612A128U01 3 Seal D333F016U01 4 Pan head screw M3 x 6 DIN 7985 D004F106AU20 5 Serrated lock washer A3 2 DIN 6798 D085G017AU32 6 Cable gland plastic grey D150A008U02 7 Spacer D375A018U01 8 Hex head screw M4 x 14 DIN 7964 SS D024G110AU20 9 Insert ring Nyltite Seal F M4 D115B00...

Страница 111: ... 3 Lower section with NPT adapter DN 100 D612A153U07 3 Cheese head screw M3 x 8 DIN 84 D002F107AU20 3 1 Clamp strap D108A003U08 4 Sheet metal screw 2 9x6 5 DIN 7981 D055E106CZ01 4 1 Serrated lock washer A3 2 DIN 6798 D085G017AU32 5 Cable gland M 20 x 1 5 standard D150A008U15 5 1 Cable gland PG 13 5 option D150A008U02 6 Cover compl D612A152U01 6 1 Cover gasket D333F022U01 6 2 Connection diagram sta...

Страница 112: ... at which the flowmeter sensor was calibrated See name plate Select the flowmeter sensor type from the list in the table Check that the letter after the model number and the nominal diameter range are correct Otherwise the transmitter will not access the correct reference data Enter the relevant meter size The values are listed for DIN and ANSI sizes Enter the reference voltage see the name plate ...

Страница 113: ...ransmitter S4 from name plate 10DS3111 A C 10DS3111 D 10DS3111 E 500 500 500 No Cs calculated Cz 0 External supply power from name plate 10D1422 10DI1425 3 1000 500 yes yes Cs calculated Cz 0 External supply power 10DS3111A 10D1462 10D1472 350 600 150 900 15 100 no use 1000 Ω adapter board calculated External supply power from name plate Important If the flow indicator shows the incorrect directio...

Страница 114: ...r to all connecting cables must be switched off Adapting the transmitter to the flowmeter sensor 10D1422 DN 3 1000 10DI1425 DN 500 1 Switch off supply power After waiting 40 minutes remove the housing cover from the field housing unit 2 Replace the shock protection cover 1 by removing the 3 screws Close switch S903 3 G00579 1 2 G00586 3 Fig 58 1 Shock protection cover 2 Cover for mounting screws 3...

Страница 115: ... x DN straight section DN Flowmeter sensor size Warm up phase 30 min 12 1 2 Maximum measuring error Pulse output DN 1 DN 2 1 25 1 12 1 of measured value 0 001 QmaxDN DN 3 DN 1000 1 10 40 Q 0 05 QmaxDN 0 5 of measured value Q 0 05 QmaxDN 0 00025 QmaxDN QmaxDN maximum flowrate for the flowmeter size 10 m s Analog output effects Same as pulse output plus 0 1 of rate 0 01 mA 0 6 5 13 1 19 7 26 2 32 8 ...

Страница 116: ...0 80 C 176 F Flowmeter sensor material Parts Standard Others Lining PTFE PFA hard rubber soft rubber ETFE Ceramic carbide Signal and ground electrode for Hard rubber Soft rubber Stainless steel 1 4571 316 Ti Hastelloy B 3 2 4600 Hastelloy C 4 2 4610 Titanium tantalum Platinum iridium Stainless steel 1 4539 904 L PTFE PFA ETFE Hastelloy C 4 2 4610 Stainless steel 1 4571 316 Ti Hastelloy B 3 2 4600 ...

Страница 117: ...eel Stainless steel 10 C 14 F 25 C 13 F 130 C 266 F 130 C 266 F Thick PTFE PFA Steel Stainless steel 10 C 14 F 25 C 13 F 130 C 266 F 130 C 266 F 180 C 356 F 180 C 356 F Ceramic carbide Steel Stainless steel 10 C 14 F 20 C 4 F 80 C 176 F 80 C 176 F G00589 TS PN 40 PN 25 PN 16 PN 10 PN 63 PN 100 30 22 10 14 10 50 30 86 50 122 70 158 90 194 110 230 130 266 150 302 170 C 338 F 0 10 20 30 40 50 60 70 8...

Страница 118: ...S 6 7 8 9 10 11 12 13 14 15 16 17 DN 700 PN 16 DN 900 PN 16 DN 800 PN 16 DN 1000 PN 16 DN 900 PN10 DN 800 PN 10 DN 700 PN 10 DN 1000 PN 10 30 20 10 0 10 20 30 40 50 60 70 80 90 C 22 4 14 32 50 68 86 104 122 140 158 176 194 F PS psi 87 0 101 5 116 0 130 5 145 0 159 5 174 0 188 5 203 0 217 5 232 0 246 5 Fig 65 Stainless steel DIN flange DN 700 DN 1000 28 40 G00220 PS bar TS DN 700 PN 16 DN 900 PN 16...

Страница 119: ...hers PFA Peek Torlon Hast C4 2 4610 1 4539 904 L for pipe conn and Tri Clamp Hast B3 2 4600 1 4539 904 L 1 4571 316 Ti Titanium tantalum Platinum iridium Flat head Pointed head DN 10 1 4539 904 L 1 8 sanitary connectors always with 2 grounding electrodes in material for signal electrodes standard Process connection material Process connection Standard Option Flange Stainless steel 1 4571 316 Ti On...

Страница 120: ...248 F JIS B2210 10K wafer type Meter size DN Material PN TS PS bar 32 100 1 4 1 4404 316 L 1 4435 316 L 1 4301 304 10 40 130 C 40 266 F 10 Material load for flange model SE21F Lining PFA G00221 PS bar TS PN 40 PN 25 PN 16 PN 10 0 5 10 15 20 25 30 35 40 45 30 20 10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 C 22 4 14 32 50 68 86 104 122 140 158 176 194 212 230 248 266 F PS psi 0 72 5 145 0 217 5 ...

Страница 121: ...ors temperature and air humidity No effect under the following conditions Temperature in range from 25 55 C 77 131 F and a relative humidity of 94 97 Shock and vibration resistance according to 60068 2 6 grouping of devices according to table C2 for general industry applications No additional effect on the following levels of vibration Frequency range 10 55 Hz amplitude max 0 15 mm Cable entry poi...

Страница 122: ...E mark The version of the meter in your possession meets the requirements of the following European directives EMC directive 2014 30 EU Low voltage directive 2014 35 EU RoHS Directive 2011 65 EU Pressure equipment directive PED 2014 68 EU Pressure equipment does not receive a CE mark indicating PED compliance on the factory tag in the event of the following conditions prevailing The maximum permis...

Страница 123: ...ut External zero return Totalizer reset External system zero no function Current output 0 4 20 mA 0 2 10 mA 0 5 mA 0 10 20 mA 4 12 20 mA Iout with alarm 0 103 3 8 mA Low High Detector e pipe ON OFF Calibrate e pipe 0 10000 Alarm e pipe ON OFF Iout with empty pipe 0 103 3 8 mA Low High Totalizer function Standard difference totalizer Display line 1 Q Q unit Q mA counter F R TAG number blank line ba...

Страница 124: ...ne Fax E mail Device details Type Serial no Reason for the return description of the defect Was this device used in conjunction with substances which pose a threat or risk to health Yes No If yes which type of contamination please place an X next to the applicable items Biological Corrosive irritating Combustible highly extremely combustible Toxic Explosive Other toxic substances Radioactive Which...

Страница 125: ......

Страница 126: ......

Страница 127: ......

Страница 128: ...8 ABB 2018 D184B140U02 Rev D ABB Limited Measurement Analytics Howard Road St Neots Cambridgeshire PE19 8EU UK Tel 44 0 870 600 6122 Fax 44 0 1480 213 339 Mail enquiries mp uk gb abb com ABB Inc Measurement Analytics 125 E County Line Road Warminster PA 18974 USA Tel 1 215 674 6000 Fax 1 215 674 7183 ABB Automation Products GmbH Measurement Analytics Dransfelder Str 2 37079 Goettingen Germany Tel ...

Отзывы: